Specifications

21
Table 12 — Configuration Mode and Sub-Mode Directory
SUB-
MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
DISP
TEST ON/OFF TEST DISPLAY LEDs See Backlight and Contrast adjustment in
Tables 21 and 22.
METR ON/OFF METRIC DISPLAY Off = English
On = Metric
LANG X LANGUAGE SELECTION Default: English
English
Espanol
Francais
Portuguese
PAS.E ENBL/DSBL PASSWORD ENABLE
PASS XXXX SERVICE PASSWORD Default: 1111
UNIT TYPE X UNIT TYPE Air Cooled (GXN,R)
Water Cooled (HXC)
Split (HXA)
Heat Machine
Heat Reclaim
TONS XXX UNIT SIZE
CAP.A XXX % CIRCUIT A % CAPACITY 30GXN,R
080, 083, 135, 138 = 54
090, 093, 108, 114, 125, 128, 153 = 59
106 = 63
150 (60 Hz) = 41
160 = 45
174, 178, 281-350 = 50
204 = 64
225 = 61 118, 163 = 55
249, 253 = 71 208 = 70
264, 268 = 67 228 = 72
30HXA,C
076, 186 = 50
086, 126 = 54
096, 116, 136, 161 = 59
106, 246 = 63
146 = 55
171 = 45
206 = 57
261 = 65
271 = 67
CMP.A X NUMBER CIRC A COMPRESSOR HXA,C076-186 = 1
HXA,C206-271 = 2
GXN,R080-178 = 1
GXN,R204-350 = 2
CMP.B X NUMBER CIRC B COMPRESSOR HXA,C076-271 = 1
GXN,R080-268 = 1
GXN,R281-350 = 2
DIS.S XX.X F DISCHARGE SUPER SETPOINT Default: 22° F DISCHARGE SUPERHEAT
FAN.S X FAN STAGING SELECT None (30HXA, 30HXC)
1 STAGE IND
2 STAGE IND (30GXN,R163, 178)
3 STAGE IND (30GXN,R281-350, 208, 228,
253, 268)
A2B1 IND (30GXN,R153, 174, 204, 225)
A3B2 IND (30GXN,R249, 264)
1 STAGE COM (30GXN,R080, 090)
2 STAGE COM (30GXN,R083, 093, 106, 108, 114,
125, 135)
3 STAGE COM (30GXN,R118, 128, 138, 150, 160)
CM.A1 XXX AMPS COMPR. A1 MUST TRIP AMPS Verify with Appendix A
CM.A2 XXX AMPS COMPR. A2 MUST TRIP AMPS Verify with Appendix A
CM.B1 XXX AMPS COMPR. B1 MUST TRIP AMPS Verify with Appendix A
CM.B2 XXX AMPS COMPR. B2 MUST TRIP AMPS Verify with Appendix A
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER