Water Dispenser User Manual

Terminals TB2-11 and TB2-12 are provided for field in-
stallation of a chilled water (fluid) pump interlock (CWPI)
and a chilled water (fluid) flow switch (CWFS). These de-
vices are to be installed in series. Contacts must be rated for
day circuit applications capable of handling a 24-vac to
50 mA load.
Accessory remote on-off switch can be wired into TB2-13
and TB2-14. To use this feature, remove the factory-installed
jumper and install the device in series. See Fig. 13 for re-
mote on-off, CWPI, and CWFS wiring. Contacts must be
rated for dry load application capable of handling a 24-vac
to 50 mA load.
Do not use interlocks or other safety device contacts
connected between TB2 terminals 13 and 14 as remote
on-off. Connection of safeties or other interlocks be-
tween these 2 terminals will result in an electrical
bypass if the REMOTE-OFF-LOCAL switch is in the
LOCAL position. If remote on-off unit control is re-
quired, a field-supplied relay must be installed in the
unit control box and wired as shown in Fig. 13. Failure
to wire the remote on-off as recommended will result in
tube freeze damage.
Terminals 2 and 3 of TB2 have been provided for a
field-supplied remote alarm (ALM). If an audible alarm is
installed, an alarm shutoff is also recommended. Contacts
are rated for 125 va at either 115 or 230 v control power. See
Fig. 13.
Terminals 4 and 5 of TB2 have been provided for a
field-supplied chilled water (fluid) pump relay (CWP). A
field-supplied power supply of appropriate voltage must be
provided. Contacts are rated for 125 va at either 115 or
230 v control power. See Fig. 13.
Terminals 1 and 6 of TB2 have been provided for a
field-supplied control relay for the remote condenser (30HXA)
or a condenser pump relay (30HXC). A field-supplied power
supply of appropriate voltage must be provided.
Step 5 — Install Accessories
ELECTRICAL Several optional control accessories are
available to provide the following features:
control transformer
cooler pump/flow switch interlock
cooler pump control
expanded display panel
remote alarm
remote on-off
pulldown control
occupancy scheduling
demand limit control
temperature reset (from occupied space or outdoor-air
temperature)
dual set point control
condenser water sensors
level II communications (CCN
[Carrier Comfort Network])
Refer to Start-Up and Operation literature and sepa-
rate accessory installation instructions for additional
information.
30HXA LOW-AMBIENT OPERATION If outdoor
ambient operating temperatures below 60 F (15 C) are ex-
pected, refer to separate installation instructions for low-
ambient operation using accessory Motormastert III control.
MINIMUM LOAD ACCESSORY If minimum load
accessory is required, use the appropriate package. Refer to
unit Price Pages or contact your local Carrier representative
for more details. For installation details, refer to separate in-
stallation instructions supplied with the accessory package.
MISCELLANEOUSACCESSORIES For applications re-
quiring special accessories, the following packages are avail-
able: control power transformer, minimum load control, sound
reduction enclosure, external vibration isolation, expanded
display, Victaulic-type connections, temperature reset sen-
sor, and chilled fluid flow switch. Refer to individual acces-
sory installation instructions for installation details.
Step 6 Leak Test Unit
30HXC UNIT These units are shipped from the factory
with a full charge of R-134a (See Tables 1A and 1B). Per-
form a leak test to ensure that leaks have not developed
during unit shipment. Dehydration of the system is not re-
quired unless the entire refrigerant charge has been lost. There
are a number of Swage-Lok fittings used on the refrigerant
piping. If a leak is detected at any of these fittings, tighten
outside nut
1
8
turn.
DO NOT OVERTIGHTEN THESE FITTINGS. Over-
tightening will result in the tube being crushed and will
cause a refrigerant system leak.
30HXA UNITS These units are shipped with a holding
charge of R-134a. Leak test and dehydrate the complete sys-
tem (including both field and factory installed piping).
Step 7 Refrigerant Charge
IMPORTANT: These units are designed for use with
R-134a only. DO NOT USE ANY OTHER refrig-
erant in these units without first consulting your
Carrier representative.
The liquid charging method is recommended for com-
plete charging or when additional charge is required.
When charging, circulate water through the condens-
er and cooler at all times to prevent freezing. Freezing
damage is considered abuse and may void the Carrier
warranty.
DO NOT OVERCHARGE system. Overcharging re-
sults in higher discharge pressure with higher cooling
fluid consumption, possible compressor damage, and higher
power consumption.
26