Instruction manual

3
There are no buried--line applications greater than 36 in. (914.4
mm).
If refrigerant tubes or indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and
moisture in the system.
Outdoor Unit Connected to Factory Approved Indoor
Unit
Outdoor unit contains correct system refrigerant charge for
operation with factory approved AHRI rated indoor unit when
connected by 15 ft. (4.57 m) of field--supplied or factory--accessory
tubing, and factory supplied filter drier. Check refrigerant charge
for maximum efficiency.
Table 1 Accessory Usage
Accessory
REQUIRED FOR LOW---AMBIENT
COOLING APPLIC ATIONS
(Below 55°F / 12.8°C)
REQUIRED FOR LONG LINE
APPLICATIONS* (Over 80 ft. / 24.38 m)
Crankcase Heater Ye s
Yes
Compressor Start Assist Capacitor and Relay Ye s Ye s
Evaporator Freeze Thermostat
Ye s
(For non---Infinity systems only)
No
Liquid Line Solenoid Valve No
See Long---Line Application Guideline
Low ---ambient Pressure Switch
Ye s
(For non---Infinity system only)
No
Support Feet Recommended No
Thermal Expansion Valve (TXV)
Hard Shutoff
Ye s Ye s
Winter Start Control
Ye s
(For non---Infinity systems only)
No
* For tubing line sets between 80 a nd 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Split--- System Longline Application Guideline.
Table 2 – Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)
UNIT SIZE
LIQUID
RATED VAPOR
up to 80 ft. (24.38 m)*
Connection and Tube
Diameter
Connection
Diameter
Rated Tube
Diameter
18, 24, 30, 3/8 3/4 3/4
36, 42, 48 3/8 7/8 7/8
60 3/8 7/8 1 --- 1 / 8
* Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance data when using different size and length linesets.
Notes:
1. Do not apply capillary tube or fixed orifice indoor coils to these units.
2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential 250 ft. (76.2 m) Total Equivalent Length),
refer to the Residential Piping and Application Guideline --- Air Conditioners and Heat Pumps using Puron refrigerant.
3. For alternate liquid line options on 18---42 size units, see Product D ata or Residential Piping and Application Guideline
the environmentally sound refrigerant
This product has been designed and manufactured to meet
Energy Star criteria for energy efficiency when matched
with appropriate coil components. However, proper
refrigerant charge and proper air flow are critical to achieve
rated capacity and efficiency. Installation of this product
should follow all manufacturing refrigerant charging and air
flow instructions. Failure to confirm proper charge and
air flow may reduce energy eff iciency and shorten
equipment life.
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
Ready for use in a Hybrid Heatr Duel Fuel system.
24ANB6