Installation manual

High Wall Type
Installation Manual
–17–
Power supply wire
Recommended wire diameter and wire length for power supply wire.
Electric characteristics
Control wire
Remote control wiring
2-core with non-polarity wire is used for wiring of the remote control wiring and group remote controls
wiring.
NOTE
Use copper supply wire.
Use UL wire rated 600V for the power supply.
Use UL wire rated 300V for the remote control wires and control wires.
CAUTION
The remote control wire (Communication line) and AC208/230V wires cannot be parallel to contact each
other and cannot be stored in the same conduits. If doing so, a trouble may be caused on the control
system due to noise or other factor.
Power supply wiring
Wire size: 2 × AWG12
Ground 1 × AWG12 or thicker
Up to 164’1” (50m)
MCA : Minimum Circuit Amps
MOCP : Maximum Overcurrent Protection (Amps)
Model Power Supply
Voltage Range (V) MCA MOCP
Min Max (A) (A)
MMK-AP0073H2UL
208/230V-1-60Hz 187 253
0.3
15
MMK-AP0093H2UL 0.3 15
MMK-AP0123H2UL 0.3 15
MMK-AP0153H2UL 0.5 15
MMK-AP0183H2UL 0.5 15
MMK-AP0243H2UL 0.5 15
Control wiring between indoor units, and outdoor
unit (2-core shielded wire)
Wire size
(Up to 3280’10” (1000m)) AWG16
(Up to 6561’8” (2000m)) AWG14
Remote control wiring, remote control inter-unit wiring Wire size: AWG20
Total wire length of remote control wiring and remote
control inter-unit wiring = L + L1 + L2 + … Ln
In case of wired type only Up to 1640’5” (500m)
In case of wireless type included Up to 1312’4” (400m)
Total wire length of remote control inter-unit wiring = L1 + L2 + … Ln Up to 656’2” (200m)
L1
L
L2 Ln
Indoor unit
Remote control inter-unit wiring
Indoor unit Indoor unit Indoor unit
Remote
control
(Max. 8 units)
Remote
control
wiring
17-EN