Error detected by TCC-LINK central control device
TCC-LINK : TOSHIBA Carrier Communication Link.
P04 P04
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
ALT High-pressure SW system operation IPDU
P05 P05
00: Detected phase loss
ALT
Phase loss error/interruption of power
supply
I/F
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
Inverter DC voltage (Vdc) error
P07 P07
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
ALT Heat sink overheat error IPDU, I/F
P10 P10 Detected indoor address ALT Indoor overflow error Indoor
P12 ALT Indoor fan motor error Indoor
P13 P13 ALT Outdoor liquid back detection error I/F
P15 P15
01: TS condition
02: TD condition
ALT Gas leak detection I/F
P17 P17 ALT Discharge temp. TD2 error I/F
P18 P18 ALT Discharge temp. TD3 error I/F
P19 P19 Detected outdoor unit number ALT 4-way valve inverse error I/F
P20 P20 ALT High-pressure protective operation I/F
P22 P22
0 :IGBT circuit
1 :Location detection circuit
error
3 :Motor lock-up error
4 : Motor current was
detected.
C :Abnormal temperature
was detected by the TH
sensor.
D :TH sensor error
E :Inverter DC voltage error
(outdoor unit fan)
Caution)
Although letters 0 to F appear
at locations indicated by “ ”,
please ignore them.
ALT Outdoor fan IPDU error IPDU
P26 P26
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
ALT G-TR short protection error IPDU
P29 P29
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
ALT
Comp position detective circuit system
error
IPDU
P31 P31 ALT
Other indoor unit error
(Group follower unit error)
Indoor
Check code Wireless remote control
Check code name Judging device
Wired
remote
control
display
Outdoor 7-segment display
Sensor block display of
receiving unit
Auxiliary code
Operation
Timer
Ready
Flash
C05
Sending error in TCC-LINK central
control device
TCC-LINK
C06
Receiving error in TCC-LINK central
control device
TCC-LINK
C12
Batch alarm of general-purpose
equipment control interface
General-purpose
equipment I/F
P30
Differs according to error contents of unit with occurrence of alarm Group control branching unit error
TCC-LINK
(L20 is displayed) Duplicated central control addresses
Check code Wireless remote control
Check code name
Judging
device
Wired
remote
control
display
Outdoor 7-segment display
Sensor block display of
receiving unit
Auxiliary code
Operation
Timer
Ready
Flash