Installation manual

High Wall Type
Installation Manual
–8–
EN
Cutting a hole and mounting
installation plate
Cutting a hole
In case of installing the refrigerant pipes from the
rear:
1. Decide the hole position for piping at 7.1”
(180 mm) from the arrow mark (Ö) on the
installation plate and drill a hole at a slight
downward slant toward outdoor side.
Pipe hole; dia.2.6” (65 mm): MMK-AP007 to
018 type
Pipe hole; dia.3.1” (80 mm): MMK-AP024
type
NOTE
To drill a wall that contains a metal lath, wire lath
or metal plate, use a pipe hole brim ring sold
separately.
Mounting the installation plate
When the installation plate is directly
mounted on the wall
1. Securely fit the installation plate onto the
wall by screwing it in the upper and lower
parts to hook up the indoor unit.
2. To mount the installation plate on a
concrete wall with anchor bolts, utilize the
anchor bolt holes as illustrated in the above
figure.
3. Install the installation plate horizontally in
the wall.
CAUTION
When the installation plate is installed with a
mounting screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the unit
falls.
In case of block, brick, concrete or similar type
walls, make 0.2” (5 mm) dia. holes in the wall.
Insert clip anchors for appropriate mounting
screws.
NOTE
Secure four corners and lower parts of the
installation plate with 6 mounting screws to
install it.
80
65
1111012101
80
65
1111012101
0.9” (23 mm)
The centre of the pipe hole is above the arrow
7.1” (180 mm)
Pipe hole
dia. 2.6” (65 mm):
AP007 to 018 type
dia. 3.1” (80 mm):
AP240 type
dia.2.6"
(65 mm)
5.2" (132 mm)
6.7" (170 mm)
1.6" (40 mm)
2.0" (50 mm)
6.7" (170 mm)
0.9" (23 mm)
3.3"(85 mm)
Anchor bolt holes
Hook
Hook
Pipe hole
Indoor unit
Thread
Weight
Mounting
Screw
Installation plate
Pipe hole
(dia. 2.6” (65 mm))
dia. 3.1” (80 mm))
Hook
6’7” (2 m) or more from floor
Fix the installation plate to the wall with screws to
make the indoor unit fit to the wall.
Projection
0.6” (15 mm) or less
Clip anchor
(local parts)
Mounting screw
0.16” (4 mm) × 1.0” (25 mm)
Anchor bolt
0.2” (5 mm) dia. hole
OK NO
GOOD
NO
GOOD
8-EN