MessageCenter MESSAGES - Continued
Message Description
START STOP LOCKED The set point has been locked into Start-Stop Operation. Continu-
ous Run can not be selected.
START-STOP MODE SELECTED Start-Stop Operation has been selected.
STATUS OK The unit is operating correctly.
TECHNICIAN RESET REQUIRED
(A21)
AL11 (Low Engine Oil Pressure) or AL12 (High Coolant Temperat-
ure) has been activated three times in the last two hours and the
unit has been locked out. The unit must be brought to a Carrier
Transicold Dealer for service.
TEST #1(to #15) XX% COMPLETE Pretrip is currently running this test and is XX% complete.
TIME SELECTION NOT CHANGED A time change was started but not entered (saved) in Configuration
List.
TRIP START ENTERED The Trip Start marker has been placed in the DataLink data record-
er.
UNIT BATTERY TOO LOW The unit battery has dropped below 7 volts for more than 10 sec-
onds.
UNIT SHUTDOWN - DOOR OPEN The unit has shutdown because the refrigerated compartment door
is open.
UNIT SHUTDOWN - SEE ALARM LIST An active shutdown alarm has shut the unit down.
UNIT SHUTDOWN - RMS1(2) The unit has shutdown because switch is open. May be connected
to a door or a remote control switch.
UNKNOWN CARD - REMOVE CARD A defective or different type of PC Card has been inserted into the
PC Card slot. The microprocessor can not recognize any data on
the card. The card may be safely removed from the micropro-
cessor.
WARNING: DIESEL RESTART ON When electric power is not available while the unit is operating in
Standby Operation, the unit will switch to Engine Operation.
WARNING: NO TEMP CONTROL The temperature sensors have failed and the unit has entered
Cargo Protect Mode. Refer to Section 4.8.1.
WRONG UNIT TYPE, REMOVE CARD A configuration PC card has been inserted into the PC Card slot.
The unit model family type on the PC card is not in the same unit
family type as the microprocessor. The card may be safely re-
moved from the microprocessor.