3.7 CONTINUOUS OPERATION
COOL DEFROST ALARM START‐STOP
ALARM LIST
SELECT
MANUAL
DEFROST
HEAT CONTINUOUS
CONTINUOUS RUN MODE SELECTED
START‐STOP/
CONTINUOUS
CONTINUOUS
OPERATION
LIGHT
1. Press the START-STOP/CONTINU-
OUS key until the CONTINUOUS
OPERATION Light on the micropro-
cessor illuminates.
2. Verify that “CONTINUOUS RUN MODE SELECTED” is dis-
played on the MessageCenter and that the CONTINUOUS
OPERATION light is illuminated. The unit is now in Continu-
ous Operation.
SETPOINT BOX TEMPERATURE
+34.5 F
-20.0
In Continuous Operation, the unit will not shutdown ex-
cept in response to a shutdown alarm. Refer to Section
4.5 for more detailed information on Continuous Opera-
tion.
The microprocessor may be configured with Start-Stop
operation tied to the set point ranges for frozen and per-
ishable loads. The START-STOP/CONTINUOUS key is
locked out if “START-STOP LOCKED” displays in the
MessageCenter when the key is pressed and the unit is
in Start-Stop Operation or “CONTINUOUS LOCKED”
displays in the MessageCenter when the key is pressed
and the unit is in Continuous Operation. Refer to
Table 52 for more information on Configurations.
If the unit fails to start after three start attempts the A 31 -
“FAILED TO START-AUTO” alarm will be activated.
While running, if the unit shuts down, an internal counter
keeps track of the shutdowns. Should the unit shutdown
three consecutive times without running a minimum of
15 minutes between shutdowns the A30 - “FAILED TO
RUN MINIMUM TIME” alarm will be activated. The shut-
down counter is cleared when the unit has run for 15 mi-
nutes.