Manual
IOM-PBE-L
2
III. PRINCIPLE OF OPERATION
1.  Movement occurs as pressure variations regis-
ter on the diaphragm. The registering pressure 
is the outlet, P
2
, or downstream pressure. The 
range spring opposes di a phragm movement. As 
SECTION III
IV. STARTUP
SECTION IV
De ter mine if the regulator is fl owing. If not, slowly 
rotate the regulator adjusting screw clockwise 
(CW) until fl ow begins.
6.  Continue to slowly open the inlet (upstream) block 
valve until fully open.
7.  Continue to slowly open the outlet (downstream) 
block valve, especially when the downstream pip-
 ing system isn't pressurized. If the outlet (down-
 stream) pressure exceeds the desired pres sure, 
close the block valve and go to Step 2, then return 
to Step 4.
8. When fl ow is established steady enough that the 
outlet (downstream) block valve is fully open, 
be gin to slowly close the bypass valve if installed.
9. Develop system fl ow to a level near its expected 
normal rate, and reset the regulator set point by 
turning the adjusting screw CW to increase outlet 
pressure, or CCW to reduce outlet pressure.
10. Reduce  system  fl ow to a minimum level and 
ob serve set point. Outlet pressure will rise from 
the set point of Step 9. The maximum rise in 
outlet pressure on decreasing fl ow should not 
exceed the stated up per limit of the range spring 
by greater than 10%; i.e. 20-80 psig (1.38-5.52 
Barg) range spring. (Example: at low fl ow  the 
outlet pressure should not exceed 88 psig (6.07 
barg), if it does, con sult factory).CAUTION
outlet pressure drops, the range spring pushes 
the dia phragm down, opening the port; as outlet 
pres sure in creas es, the diaphragm pushes up 
and the port opening clos es.
2.  A complete diaphragm failure will cause the reg u-
 la tor to fail open. 
V. SHUTDOWN
1.  On systems with a bypass valve, and where sys-
 tem pressure is to be main tained as the reg u la tor 
is shut down, slowly open the bypass valve while 
closing the inlet (up stream) block valve. Fully 
close the inlet (up stream) block valve. (When on 
bypass, the sys tem pres sure must be con stant ly 
observed and man u al ly reg u lat ed. Close the 
outlet (down stream) block valve.
2.  If the regulator and system are to both be shut 
down, slowly close the inlet (upstream) block 
valve. Close the outlet (downstream) valve only 
if reg u la tor re mov al is required.
SECTION V
 CAUTION
The maximum outlet pressure is list ed on the name plate 
as the upper range spring pres sure level, and is the rec om -
mend ed "upper operative limit" for the sens ing diaphragm 
(See Section IV. Startup, Step 7). Higher press ures could 
dam age the di a phragm. (Field hydro static tests fre quent ly 
de stroy dia phragms. DO NOT HYDRO STATIC TEST THRU 
AN IN STALLED UNIT; ISO LATE FROM TEST.)
 CAUTION
Do not walk away and leave a bypassed reg u la tor unat-
tended.
1.  Start with the block valves closed. A by pass valve 
may be used to maintain out let pres sure in the 
down stream sys tem without changing the fol low-
 ing steps.
2.  Relax the range spring by turning the adjusting 
screw counter clockwise (CCW) a minimum of 
three (3) full revolutions. This reduces the outlet 
(down stream) pres sure set point.
3.  If it is a “hot” piping system, and equipped with 
a bypass valve, slowly open the bypass valve 
to preheat the system piping and to allow slow 
ex pan sion of the piping. Closely monitor outlet 
(down stream) pres sure via gauge to ensure not 
over-pressurizing. NOTE: If no bypass valve is 
in stalled, extra caution should be used in starting 
up a cold system; i.e. do everything slowly.
4.  Crack open the outlet (downstream) block valve.
5.  Slowly open the inlet (upstream) block valve ob-
 serv ing the outlet (downstream) pressure gauge.  








