Technical Specifications

ESR-3566
|
Most Widely Accepted and Trusted Page 2 of 3
mesh metal lath conforming to ASTM C847; a 3.4 lb/yd
2
(1.8 kg/m
2
),
3
/
8-
inch thick ribbed lath conforming to ASTM
C847; or a 1.4 lb/yd
2
(0.760 kg/m
2
) galvanized woven wire
mesh conforming to ASTM C1032. Lath may be self-furred
or non-furred, provided furring or furring fasteners are
used. When the cement plaster backing is installed over
open studs, a paper back lath must be used. All lath
must be installed over the water-resistive barriers by
following lath manufacturer's installation guidelines and
recommendations. Lath or mesh must be fastened to each
of the wall studs as required by ASTM C1063 and IRC
section R703.6.1. Fasteners must be spaced a maximum
of 6 inches (153 mm) on center.
For attaching lath to wood studs, fasteners must be
galvanized nails having a minimum shank diameter of
0.120-inch, a minimum head diameter of
7
/
16
-inch
(11.1 mm) and sufficient length to penetrate the studs a
minimum of
3
/
4
-inch (19.1 mm). Wood studs must have a
minimum specific gravity of 0.42. For attaching lath to steel
studs, fasteners must be a minimum of #8 corrosion
resistant self-drilling, tapping screws complying with ASTM
C954 and having sufficient length to protrude a minimum of
3
/
8
inch (9.5 mm) through the stud. Steel studs must be a
minimum of 33 mils thick.
A scratch coat of Type S mortar (cement plaster)
complying with ASTM C926 must be applied over the lath
to a thickness of
1
/
2
inch to
3
/
4
inch (12.7 to 19.1 mm). The
scratch coat must be scored horizontally in accordance
with the manufacturer’s published installation instructions,
and must be allowed to cure in accordance with IBC
Section 2512.6, prior to the application of the veneer units.
4.2.2 Installation over Concrete and Masonry: The
veneer units may be applied over a concrete or masonry
backing, provided lath and a cement plaster scratch coat
are used. The lath must be corrosion-resistant metal lath
complying with ASTM C847, or 1.4 lb/yd
2
(0.760 kg/m
2
),
corrosion-resistant, woven wire plaster base complying
with ASTM C1032. The lath must be fastened to the wall in
accordance with Section 7.10 of ASTM C1063, and IRC
Section R703.6.1, as applicable. The fasteners must be
spaced a maximum of 6 inches (152 mm) on center
vertically and 16 inches (406 mm) on center horizontally.
The gravity load (shear) capacity and negative wind load
(pull-out) capacity of the proprietary fasteners must be
justified to the satisfaction of the code official. The scratch
coat must be applied as described in Section 4.2.1.
4.3 Application of Veneer Units:
Prior to the application of the veneer units, the scratch coat
or other backing and the back of the veneer units must be
moistened in accordance with the manufacturer’s
instructions. A minimum
1
/
2
-inch-thick (12.7 mm) setting
bed of Type S mortar must be applied to the back of the
veneer units, and the veneer units must be pressed firmly
in place, squeezing the mortar out around all veneer unit
edges. For grouted patterns, joints between veneer units
must be grouted and tooled in accordance with the veneer
manufacturer’s published installation instructions.
5.0 CONDITIONS OF USE
The precast stone veneer described in this report complies
with, or is a suitable alternative to what is specified in,
those codes listed in Section 1.0 of this report, subject to
the following conditions:
5.1 Installation must comply with this report, the
manufacturer’s published installation instructions and
the applicable code. In the event of a conflict between
the manufacturer’s published installation instructions
and this report, this report governs.
5.2 The use of the precast stone veneer has been
evaluated for installation on walls with cement plaster.
5.3 Expansion or control joints, used to limit the effect of
differential movement of supports on the veneer
system, are to be specified by the architect, designer
or veneer manufacturer, in that order. Consideration
must also be given to movement caused by
temperature change, shrinkage, creep and deflection.
5.4 In jurisdictions adopting the IBC, the supporting wall
must be designed to support the installed weight of
the veneer system, including veneer, setting bed and
cement plaster backing, as applicable. At wall
openings, the supporting members must be designed
to limit deflection to
1
/
600
of the span of the supporting
members.
5.5 In jurisdictions adopting the IRC, where the seismic
provisions of IRC Section R301.2.2 apply, the
average weight of the wall supporting the precast
stone veneer, including the weight of the veneer
system, must be determined. When this weight
exceeds the applicable limits of IRC Section
R301.2.2.2.1, an engineered design of the wall
construction must be performed in accordance with
IRC Section R301.1.3.
6.0 EVIDENCE SUBMITTED
Data in accordance with the ICC-ES Acceptance Criteria
for Precast Stone Veneer (AC51), dated February 2008
(editorially revised April 2012).
7.0 IDENTIFICATION
Boxes of precast stone veneer units are identified with the
manufacturer’s name (Norse Building Products), the
product name (Cast Natural Stone); the pattern name, the
manufacturing date, and the evaluation report number
(ESR-3566).
8.0 OTHER CODES
8.1 Evaluation Scope:
In addition to the codes referenced in Section 1.0, the
products described in this report were evaluated for
compliance with the following codes:
2009 International Building Code
®
(2009 IBC)
2009 International Residential Code
®
(2009 IRC)
The Cast Natural Stone products described in this report
comply with, or are suitable alternatives to what is
specified in, the codes listed above, subject to the
provisions of Sections 8.2 through 8.7.
8.2 Uses:
See Section 2.0.
8.3 Description:
See Section 3.0.
8.4 Installation:
8.4.1 General: See Section 4.1.
8.4.2 Preparation of Backing: See Section 4.2
8.4.2.1 Installation over Sheathing or Open Studs:
Replace the 1
st
paragraph of Section 4.2.1 with the
following: For exterior installations, the cement plaster
backing must be installed over a water-resistive barrier
complying with 2009 IBC Sections 1404.2 and 2510.6 or
2009 IRC Sections R703.2 and R703.6.3, as applicable.
Also, flashing must be installed as required by 2009 IBC
Section 1405.4 or 2009 IRC Section R703.8, as applicable,