Control Panel – Service
The fuel valve (1) can be accessed without
removing the control panel. To remove the fuel
valve, drain the fuel from the fuel tank into an
appropriate container. Start the engine and let
the engine run out of fuel. Turn the generator
switch to the off “0” position.
Open the engine access door. Move the hose
clamps that hold the fuel lines to the fuel valve to
the center of the fuel lines. Remove the fuel
lines from the fuel valve. Remove the clip from
the rear of the control panel face. Remove the
fuel valve by pushing it backwards. Reinstall in
reverse order.
Remove the bolts (1). Pull the control panel
cover forward slowly. Make sure that the cables
move freely and are not damaged. Tag the wires
to identify them and then disconnect the wiring
harnesses. Remove the front cover and place on
a surface that will protect the panel from
damage.
Choke Knob:
The choke control is held to the rear of the panel
with nuts. Remove the choke knob and cable
from the front of the panel, and remove the nuts
that hold the choke to the panel. Remove the
choke control from the rear of the panel.
Reinstall in reverse order.
Circuit Breakers:
Each circuit breaker is held to the panel with a
half nut located on the front of the panel. Tag the
wires to identify them and then disconnect the
circuit breaker. Remove the half nut from the
front of the panel then remove the circuit breaker
from the rear of the panel.
Display:
The display is held in place by hot melt glue.
Disconnect the display from the wiring harness
and remove the glue. Remove the display from
the front of the panel.
Fuse:
The generator switch has a 15 Amp fuse located
in an inline fuse holder.
Generator Switch:
The generator switch is held to the panel with
nuts. Disconnect the wiring, remove the knob
from the front of the panel, and remove the nuts.
Remove the generator switch from the rear of
the panel.