User Manual

Thermal heat alarm device
Commercial reference: 3103
Developed by CAVIUS
This Thermal Heat Alarm is designed for areas not
suitable for smoke alarms due to high risk of false
alarms such as; kitchens, garages or workshops.
PLEASE READ THE USER GUIDE
CAREFULLY BEFORE INSTALLATION AND
RETAIN FOR FUTURE USE.
SAFETY INSTRUCTIONS
The device comes with a 3V lithium battery. Bat-
teries are to be handled with care and battery pow-
ered devices should be kept out of reach of chil-
dren. Do not try to recharge or burn the batteries.
TECHNICAL INFORMATION
Cavius heat alarm detects:
1) rapidly increased temperature level
2) absolute heat level of 58 degrees C.
The maximum number of alarms that can be inter-
linked within a house group are 32.
Please note: These must be alarms from the CAVIUS
Wireless Alarm Family.
The distance between interlinked alarms depends
on the house layout and they should always be
tested after installation. It is not advised to get
more than 10m distance between two alarms.
Diameter: 65mm. Height: 44mm.
The alarm is powered by a replaceable 3v
CR123A lithium battery.
1. HOW TO SET UP AND CONNECT ALARMS:
Start by pulling out the battery isolation strip as
shown.
Please note: The product label must not be
removed as it contains important information
regarding the product.
All alarms that need to be connected in the
house should be put into ‘Learn Mode’ by sliding
the switch on the back of the alarm to the ‘Learn
Mode’ position.
The red LED will light up to indicate that ‘Learn
Mode’ has been selected.
Please note that when the alarms are placed
in ‘Learn Mode’ they can’t be inserted into the
mounting base.
Do not take out the battery during ‘Learn Mode’ as
this will interrupt the learn process.
Press and hold the test button at one alarm only,
until it beeps and the LED ashes. This alarm will
become the master and will start sending out a
specic house code to the other alarms.
As the other alarms receive the specic house
code, they will also ash the LED light.
When the red LED light flashes on all alarms,
they are connected and MUST BE SWITCHED
OUT OF ‘LEARN MODE’ and installed.
Label the original “Learn” alarm in order to easily
add new CAVIUS Wireless Family alarms to the
system.
2. THE BEST AREAS TO INSTALL THE HEAT
ALARM:
Areas not suitable for smoke alarms due to high
risk of false alarms
• Kitchen area
• Bathroom
• Garage or workshop
Additional alarms increase the security.
3. AREAS WHERE NOT TO INSTALL HEAT-
ALARMS:
• In rooms where the temperature goes outside
-10ºC to +50ºC.
• Bedrooms
• Lounge
• Dining room
• Hallway
• Family room
NOTE: In areas where smoldering res occur
over aming res, photoelectric smoke alarms
are still the best to be installed.
4. PLACEMENT:
The heat alarm is design to be installed on a ceiling
or wall. Do not install to close to the oven/hob/
stove (see drawing).
For wall installation:
For celling installation:
5. INSTALLING THE HEAT ALARM:
Detach the alarm from the mounting base by
twisting counter clockwise.
Use the mounting base ring to mark the screw
holes on the ceiling or the wall.
UK
DO NOT
REMOVE THE
PRODUCT LABEL
ISOLATION
STRIP
MARK UP
SCREW HOLES
WITH A PEN
USE THE
ENCLOSED
SCREWS AND
PLUGS
MOUNTING
BASE
TEST BUTTON
RED LED
THERMISTOR
Peak ceiling
Minimum 50cm
from peak
Minimum 30cm and
maximum 50cm from
ceiling
Wall
Ceiling
Minimum 30cm
and maximum 50cm
from stove
Ceiling
Minimum 50cm
from wall
Wall
Ceiling
LEARN MODE
NORMAL MODE