Product specifications
Device Management PROFIBUS & HART
3BDS011222-510 B 249
Insert PROFIBUS Device Type Objects in 800xA Plant Explorer.
1. Open Plant Explorer.
2. Switch to Control Structure.
3. Open the substructure below the Project object.
4. To insert a PROFIBUS Device Type Object on the CI854, select the CI854
Hardware object.
5. Right-click on the mouse and select New Object in the context menu.
6. Browse to the required PROFIBUS master object in the hardware library
catalog, e.g. ABB_TFx12_YP0_v1_0.
7. Enter the PROFIBUS address of the object inserted, e.g. 20, in the name box.
It is recommended to always use Control Builder M to create instances of
PROFIBUS device types. For details, refer to Insert PROFIBUS Device Type
Objects on page 251.
Master and Module Objects are described in the related release notes of each
Device Type Object installed via device Library Wizard.
Figure 140. Select PROFIBUS master object