Product specifications

Device Management PROFIBUS & HART
3BDS011222-510 B 261
6. Change the name of the service group, if required.
7. Click Add....
8. Select the Connectivity Server system node on which the OPC Server
PROFIBUS/HART shall be executed.
9. Click OK in the main window.
10. The OPC Server is now configured for data access to device internal data via
OPC communication.
The service group name can be found under Service Structure > Services >
OpcDA_Connector.
Example of a service group name: FBB_OPC_ControlNetwork1
Each control network needs a unique service group name and shall not given
twice in the system
Figure 149. Adding a Service Provider
If redundant Connectivity Servers are used in the system they have to be assigned
to the same Control Network. Repeat steps 1 to 10 for each redundant
Connectivity Server.
If more than one Control Network is instantiated, repeat steps 1 to 10 for these
Control Networks also.
Different service group names as well as different Connectivity Servers must be
used.