Product specifications
Device Management PROFIBUS & HART
3BDS011222-510 B 263
8. Select Configure OPC Server.
9. The message window indicates the current status of the configuration.
10. The system nodes containing the Device Management PROFIBUS & HART
software, now have direct access to device data via the OPC Server.
OPC Timing Configuration.
The OPC Server PROFIBUS/HART cycle time mainly depends on the number of
devices and the loaded asset monitors in the Asset Optimization server, but also on
the CPU load of the controllers, and the communication load between Connectivity
Server and controllers. After configuration of the OPC Server PROFIBUS/HART
through Fieldbus Management aspect general information can be shown in OPC
Server Statistics and OPC Timing Statistics.
Figure 151. Configuring the OPC Server
If more than one Control Network for AC 800M or Multiplexer is available in the
800xA System, the OPC Server PROFIBUS/HART needs to be configured for
each Network, if applicable.
Changes in the topology require a re-configuration of the OPC Server.
Update Time / Update Rate means also Cycle Time as shown in some 800xA
windows and menus in this section.