Product specifications

Device Management FOUNDATION Fieldbus
274 3BDS011222-510 B
8. After a successful check for plausibility, save the FF libraries by means of FF
Object editor > Save.
9. Exit Fieldbus Builder FF by FF Object editor > Exit
10. Return to the Plant Explorer Workplace and select the FFUpload aspect.
11. Click Upload.
The upload mirrors the FF class objects checked in Fieldbus Builder FF to the
Object Type Structure in the Plant Explorer Workplace.
12. After a successful upload, the green traffic light symbol indicates that the FF
libraries have been synchronized.
Step 2: Create and Configure an HSE Subnet
An FF network consists of at least one HSE subnet, HSE linking devices and any
number of H1 links as well as one OPC Server FF for communication of System
800xA objects with the FF network. An HSEHostCI860 device enables data
exchange between the FF network and an AC800M controller.
HSE linking devices, HSEHostCI860 Devices and OPC Server FF will be
connected directly to the HSE subnet. HSE linking devices connect the H1 links to
the HSE subnet. The H1 devices are connected to the H1 links.
An HSE subnet is created in Plant Explorer Control Structure. It can be edited by
means of Fieldbus Builder FF as well as within Plant Explorer Workplace.
To create an HSE subnet, follow the procedure below.
Step 2a: Create HSE Subnet
1. Use the Structure Selector in the Plant Explorer Workplace to open the Control
Structure.
2. Select the Root object and insert a new object with New Object.