Product specifications
Device Management FOUNDATION Fieldbus
290 3BDS011222-510 B
c. enter alarm texts for FF Process alarms (refer to Figure 171).
Configure Data Exchange with AC 800M Controller
15. Configure the HSEHostCI860 object for data exchange with the AC 800M
controller following the steps below.
a. Select the Signal list by means of Tools > Signal List.
b. Select the signals to be configured. Multi selection is possible.
c. Check the Host by which the signal shall be used. If the communication
direction is
IEC61131 -> FF, check, whether the source parameter is set to
“yes”. Refer to Figure 172
Figure 171. Alarm Parameters Tab