Product specifications
Device Management FOUNDATION Fieldbus
292 3BDS011222-510 B
Signals displays read only the assigned signals and its configuration (see
Figure 173).
The thus defined channels of the CI860 module can be assigned with I/O
variables in Control Builder M.
Schedule
A schedule which includes the time sequence of the function blocks and
communications from FF signals is automatically generated on storage of the FF
Application object. The contents of the schedule are based on the created FF
Application and the performance specifications of the H1 devices used. To display,
Figure 173. Example of an HSEHostCI860 Configuration