Product specifications

Device Management FOUNDATION Fieldbus
298 3BDS011222-510 B
on-line version check has been performed yet (e.g. because it was not
reserved).
It is recommended not to change the default Global Download settings which
will result in an incremental download with block parameters not being loaded
and the LAS on the H1 links not being stopped.
15. Start the download by means of Start, then press Continue.
The progress of the loading operation is indicated in a separate progress and
results dialog (refer to Figure 178).
16. Press Close button to close the Online dialog.
Display and Modify Online Data (Optional)
After the FF Application and the OPC Server FF have been successfully
downloaded, online data for inputs and outputs and for block parameters are
available from the devices.
17. Display online data for inputs or outputs:
Default Global Download settings do not include block parameters. To include
block parameters select Changed parameters or All parameters in the Block
Parameters Download settings.
Figure 178. Download to Device