The column Value shows the Current values, a parameter value displayed with
a yellow background indicates that the current value read from the device is
different from the configured value in the Fieldbus Builder FF database. The
configured values are displayed in the column Configuration Value at the
right end of the table.
In commissioning mode methods are processing on the current values.
Methods are provided by the device vendors to handle complex device
functions and are not available for all devices.
19. To change values of individual parameters:
a. Change the value in the value field.
b. Click Apply to write the new value to the H1 device or
c. Click Cancel to discard the changed value and close the dialog.
d. Click OK to write the new value to the H1 device and close the dialog.
e. Closing the Dialog by OK or Cancel will open a new dialog with the
option to write all changes made in the parameter dialog into the Fieldbus
Builder FF database.
20. Current values in the H1 device which are not in the Fieldbus Builder FF
database (highlighted with yellow background) can be loaded into the database
as follows:
a. Mark one or more lines in the parameter dialog.
b. Open the context menu.
c. Start the transfer of the data by means of Upload marked.
For the commissioning of your FF Application, compare the Actual and Target
mode of the individual blocks. Actual and Target mode can differ from each
other, dependent on the signal statuses at the inputs of a block.
In this case, check the cause for example, if a sensor is not connected to the
device.
For easily comparing and reconciling block parameters in the database and in the
devices use the Upload from Device tab of the Online dialog described in System
800xA Device Management, FOUNDATION Fieldbus Configuration
(3BDD012902*).