Data Exchange Protocol Without Acknowledge
322 3BDS011222-510 B
Figure 194 shows the detailed view of protocol work flow.
Characteristics of the protocol is listed below:
A protocol cycle is always initiated by the PLC. It will prepare data and raise
Command bit when the state is 0.
PLC will lower its Command bit by itself. The data will be lost, if the PC has
not read the data at that time.
PLC can TRIGGER PC with the same Command bit status at some specified
interval. (i.e. It may increment Retry Counter and write the changed TRIGGER
word to the PC repeatedly).
This protocol is also prepared with a simple transaction control feature.
Transaction Counter occupies 2 most significant bytes of the TRIGGER word.
If PLC increments Transaction Counter between protocol cycles (with
Figure 194. Data Exchange Protocol without Acknowledge, detailed description