Reserve the diagram by selecting File > Reserve Diagram to get exclusive modify
access to the diagram, and then insert the required Function Components listed in
Table 3 into the Function Diagram.
a. Navigate to a Functional Component Object Type in Object Type
Structure, for example to Object Types\Control System\AC 800M/C
Connect\Libraries\ProcessObjExtLib 2.2-1\Control Module Types\PidCC.
b. Drag and drop the PidCC into the Function Designer drawing area.
c. In the New Component Name dialog box, enter a valid name and
description. Keep the given Data Flow Order defaults. For information
about data flow order, refer to Configuring the Data Flow Order on page
49.
d. Click OK. The graphical block symbol for this Function Component
appears on the diagram. Name and Description ports are connected to the
strings you have entered. Other ports are still hidden.
3. Connect the Function Components according to column Additional Action of
Table 3.
a. Press the left mouse button on the source port.
b. Move the mouse on the sink port or on an already existing connection to
the sink port.
c. Release the mouse button.
The graphical connection link gets automatically routed.
Function Designer inserts the required application libraries into the control
project and connects them to the applications as far as possible automatically.
User needs to do this manually (refer to Insert Application Libraries on page 31
and Connect Application Libraries on page 32) only if, after configuration data
generation, red triangles appear in Control Builder M for objects resulting from
Function Designer.