Product specifications

Integrating OPC Servers into 800xA
3BDS011222-510 B 451
If the OPC AE server supports refresh, the Supports Refresh check box
should be selected.
If the selected Alarm Manager relies on refresh from OPC server
whenever a connection to the server has been re-established (and alarms
not part of the refresh will be thrown away).
If the OPC AE server supports disabling the Supports Disabling check
box should be selected.
If this option is selected, the Disable/Enable Alarm function will be
available based on user permissions.
The Supports Disabling on Condition is a non OPC standard feature
which is not expected to be supported by third party OPC servers. If
selected, the OPC server must support Disable/Enable with
<source:condition> as source.
If the event collector is not set up as a redundant pair the Require Dual
Acknowledge has no effect.
Figure 276. Alarm Collection Definition