Product specifications
Integrating OPC Servers into 800xA
3BDS011222-510 B 455
Source Object Interceptor (optional step). By default the Event Collector will try
to find an object with a name equal to the source name of the event. The Source
Object Interceptor configurations can be used to limit the scope/set of objects that is
searched and to create new objects if no matching source name is found. If the
Source Object Interceptor configuration is not used, events from unknown sources
will be discarded. The Source Object Interceptor aspect is created by adding a new
Source Configuration in the Special Configuration Tab of the Event Collector
service group.
Use the Default Root Node configuration to limit the scope/set of objects that is
searched.
Select the Create source object if not found check box to create a new object if no
matching source object is found. The name of the new object will be the source
name of the event. The new object will be created under the Lost and Found object if
the Default Root Node is not configured or not uploaded.
Figure 279. Source Object Interceptor Configuration