Control Logic Section 2 Configuration
50 3BDS011222-510 B
4. Click Apply to assign the new Data Flow Order to the respective function
components.
5. Click Close to exit.
Refer to System 800xA Engineering, Engineering Studio Function Designer
(3BDS011224*), Section 2 - Configuration for more information on the data flow
order.
Generating Configuration Data
Click the Code Generation / Code Generation (Full Build) icon from
the Quick Access menu/tool bar.
Message windows show the progress during generation.
Alternatively use File > Generate Configuration Data (Full Build) or open the
Config View of the Allocatable Group aspect from the context menu of the aspect
in Engineering Workplace and click Generate Configuration Data (Full Build).
Downloading and Testing the Function Diagram
1. To download the loop in Control Builder M Professional:
a. Ensure that the Control Project, the affected applications and the affected
controllers are reserved.
The Data Flow Order of blocks on a diagram is crucial for execution. It is
suggested to ensure that the order is as intended, for example, by clicking the
Generate button in the Data Flow Order in Allocatable Group dialog.
The Generate button can be used to sort the function components available in the
Function Diagram according to the default Data Flow Order. The default order is
calculated according to the rule “left up to right down”. After generating the
default Data Flow Order, click Apply to assign the Data Flow Order accordingly.
If DisplayDetailsOnGenerateConfigData is set to True in the Function Settings
aspect of: Object Type Structure\Object Types\Functional Planning\Settings, and
if errors occur, the message window stays open to allow the user to inspect the
error messages. Click Close to continue.