Product specifications
Examples of Object Types
514 3BDS011222-510 B
4. Add a CBM_SignalInformation aspect and configure
Allocation Type of IO Signal = Connect to Local Variable on Diagram of
Structured Data Type, Variable Data Type = IO_SAgitator, Attributes= retain
as shown in Figure 320.
5. Create a Formal Instance List object for the Functional Structure below the
IOSAgitator object type.
6. Add for each structured data type component the appropriate signal object
below the Formal Instance List of object type IOSAgitator (see Figure 319).
a. The Relative Name should be the component Name of the Data Type (e.g.
FB1, FB0, Cmd0, Cmd1, Current).
b. Each IO signal should get an additional Name aspect which has the Signal
Group name as prefix with an additional suffix.
c. For each IO signal the CBM_SignalInformation aspect has to be set as
"Connect to Application Global Variable of Structured Data Type (Signal
Group)". See step 4. This will create a global variable during code
generation in the Application.
Figure 320. Signal Information