Product specifications

Building Reuse Instructions
516 3BDS011222-510 B
h. In the Aspect Properties dialog click on the first row dealing with IN port.
i. Shift click on the last row dealing with IN port.
j. Right click in the selected area and click Remove Property.
k. Click on the value cell of property Value.DataType.
l. Replace data type BoolIO by IO_SAgitator.
m. In the Aspect Properties dialog press OK.
3. In the Function Designer window press Save and Close on window level to
exit.
4. Open the Diagram view from the Function aspect and add a diagram template,
for example A3 Landscape. The child signal objects will be displayed on the
diagram.
Building Reuse Instructions
To build a Reuse Instruction and to generate it into an object type you have to
perform the principal steps:
1. Open the Reuse Design Structure.
2. Create a new object of type Reuse Instruction, name it at your choice.
3. Define needed substitution variables in the Reuse Substitution aspect as
required by the solution you want to implement as a Reuse Instruction.
4. If you need a Reuse Global Operation or Reuse Pre Operations or Reuse Post
Operations insert an aspect of the corresponding aspect category into the Reuse
Instruction object.
5. On the Reuse Global Operation aspect you enter the operation code in
VBScript.
6. On the Reuse Pre Operations or Reuse Post Operations aspect you enter the
operations using the New button as required by your solution by selecting
prepared operations from three different categories:
General Operations (New Object, New Aspect, Modify Property, Script Block,
Insert Object, Overwrite Aspect),
Object Type Operations (New Object Type, Modify Aspect Control, Modify