Installation manual

L2 will come back on, indicating that the STATUS has been updated.
34. To set the COUNT value of the Auto-close timer, Pedestrian Auto-close time, Courtesy light timer,
Auto-close override timer, Pre-flashing time, Collision counter, or the Leaf delay time Features:
Press and hold the TEST button while monitoring the STATUS light. After a slight pause, the
STATUS light will start flashing at an even rate. Count all the flashes, and release the TEST button
when the number of flashes is the same as the COUNT value required.
Example 2:
Set the AUTO-CLOSE TIME to 10 seconds (That is Feature number 3, to a COUNT value of
10):
First select the Feature number 3 as in steps 30 to 32. Then press and hold the TEST button
while monitoring the STATUS light:
After a slight pause, the STATUS light will start flashing regularly:
Flash (1), Flash (2), Flash (3), Flash (4), Flash (5), Flash (6), ….........Flash (9),
Flash (10).
At this moment release the TEST button to give a COUNT value of 10. This sets the auto-
close timer to 10 seconds.
L2 will come back on, indicating that the COUNT has been updated.
Controller Features
The terminology "FEATURE 2-2" refers to Feature number 2 with a status of 2. “FEATURE 3- COUNT”
refers to Feature number 3, with a user specified COUNT value.
Auto-close
This can be programmed ON (FEATURE 2-1) or OFF (FEATURE 2-2). The factory default is OFF. Auto-
close has the function of automatically closing a gate after a preset auto-close time. Auto-close must not
be turned OFF in condominium or PIRAC mode.
A gate that is stopped while opening will always auto-close. A gate that is stopped while closing will
remain where it is stopped indefinitely.
This time is set in FEATURE 3-COUNT. It can be set from 1 to 255 seconds. It is possible for the user to
temporarily turn off auto-close when the mode of operation is either STANDARD and REVERSING. This is
done by applying an impulse to the TRG input at the time of opening the gate, for a period of time longer
than the AUTO-CLOSE OVERRIDE TIME as set in FEATURE 8-COUNT. To provide feedback that the
override signal has operated, the gate will stop opening after the override time. The instant the impulse is
removed the gate will complete its opening cycle. The auto-close is now off and the gate will remain open
indefinitely. The next impulse received on TRG will initiate the closing cycle and the auto-close is
automatically re-instated.
Mode of Operation
It is possible to select 4 different modes of operation: STANDARD, CONDOMINIUM, PIRAC and
REVERSING (FEATURE 4-1 to 4-4). Only one mode can be activated at any one time. All the modes are
triggered by the contact present between the TRG input terminal and the COM terminal.
STANDARD MODE (FEATURE 4-1) (This is the factory default mode) - A trigger impulse will
cause the gate to start moving (either open or closed depending on its position). A second