• When the PED input is triggered the pillar light flashes for an adjustable (1 to 255 seconds) pre-
flash time (FEATURE 11 - COUNT) before the pedestrian gate opens. (Default pre-f;ash time is 2
seconds).
• The contact can be used to operate a lamp, which will warn that the gate is about to open.
Selection of pre-flashing is done in FEATURE 10. Three modes and OFF are selectable (The
factory default is OFF):
Mode 1 - Light comes on only while gates are in motion.
Mode 2 - Light flashes at 1Hz for the pre-flash time and then flashes in synchronism with the
STATUS LED while the gates are in motion.
Mode 3 - Light comes on for the pre-flash time and while the gates are in motion.
Positive Close Mode:
Setting positive close mode to ON (FEATURE 9-1) (default is OFF, FEATURE 9-2) will allow the gate to
drive up hard to an end stop without causing the collision circuitry to operate. This Feature operates
only during the last 10 degrees of arm travel in the closing moe.
Leaf Delay:
(Feature 13 & 14) It is possible to select 3 different types of leaf delay. Feature 14 selects the delay time.
FEATURE 13-1 Will delay the slave motor during its opening cycle only for the leaf delay time.
FEATURE 13-2 Will delay the master motor during its closing cycle. This is to ensure that the
slave gate will reach the fully closed positions before the master leaf. For
example, in situations where the master gate has a flap which must close
against the slave gate.
FEATURE 13-3 Will cause the slave gate to delay on opening and the master gate to delay on
closing.
FEATURE 13-4 Turns all leaf delays OFF (Default setting).
FEATURE 14-COUNT Allows the leaf delay to be set from 1 to 255 seconds. The default delay time is
2 seconds.
NOTE: The solenoid lock strike time is set via the leaf delay timer.
All the known causes of problems are listed, according to the step number in the gate limits setup
instructions.