Installation manual

Page 35
Set-up Troubleshooting GuideSet-up Troubleshooting GuideSet-up Troubleshooting Guide
SET-UP
STEP
PROBLEM POSSIBLE CAUSES & SOLUTIONS TO PROBLEM
14 or
29
SET light is not on:
L2 is not on:
STATUS light did not
flash 5 times:
L1 is flashing:
16
STATUS light flashes 5
times and L2 turns on.
17
There is a click but the
motor does not turn. The
STATUS light flashes
rapidly, then flashes 5
times. L2 turns on.
There is a click, the
motor turns but the gate
does nor move.
Check that the SET link is correctly fitted. Fit and remove the link
a few times to ensure good contact.
All sources of power on the card must be removed. Check by
confirming that all the lights turn off, before reconnecting the
power with the set link fitted.
The controller did not “boot-up” correctly. Try to fit the charger
plug before reconnecting the battery.
Check for and remove latching inputs on the TRG terminal then
restart from step 11.
This could be due to:
The gate not being correctly positioned. Move the gate to its
half way position and restart from step 14.
The origin not being set correctly. Restart the setup from
step 14.
A faulty origin PCB or cable. To check, go out of program-
ming mode by removing the SET link. Then insert the origin
setup tool, turn the tool a full revolution while monitoring L1
and L2. If either L1 or L2 changed state during the
adjustment, then the origin system for the motor tested is
OK. restart the setup from step 4.
If not, check the status of all plugs and wiring. If the problem
is not resolved then the sensor, cable or controller might be
faulty.
This could be due to:
The motor not being connected to the controller, or
The motor fuse could be blown, or
The motor is faulty. Check motor by connecting motor leads
directly to the battery.
Check for loose connections or corrosion on battery
terminals.
2
The motor cables are too thin. They must be 2,5mm
Check for low battery condition by following procedure A on
page 41.
Correct the problem, remove and refit the SET link and start
from step 17.
The manual release mechanism is still in manual mode. The
manual release must be unscrewed as in step 10.
Not enough time is allowed for the manual release to re-engage.
To continue setup, press the TEST button as in step 17