Set-up Troubleshooting Guide Continued...
17
(continued)
Motor briefly starts and
then stops, and STATUS
flashes 5 times.
Motor starts then stops
after 1 second (STATUS
flashes 5 times)
18
Light L1 is on when
setting the Master, or L2
is on when setting the
Slave motor:
19
The gate does not open,
STATUS light flashes 5
times and L2 turns on.
20
Light L1 is off when
setting the Master, or L2
is off when setting the
Slave motor:
24
The gate stopped short
of either the open or
closed position:
The gate does not close
when pressing TEST:
The gates do not close
simultaneously:
23
L2 and SET did not go off
The battery is not connected. Correct the problem, remove and
refit the SET link and start from step 17.
Faulty DOSS sensor or cable.
The DOSS sensor system is faulty. Is the DOSS harness
plugged in? If so, there could be a fault on the sensor, cable or
controller.
The leaf has not passed through the origin yet. In which case:
Either keep on pressing and holding the test button until the
required gate closed position is reached with L1 off, or
Mechanically reset the gate origin by restarting from step 4.
The battery is discharged. Replace or charge the battery.
The leaf has not passed through the origin yet. In which case:
Either keep on pressing and holding the test button until the
required gate closed position is reached with L1 or L2 on, or
Mechanically reset the gate origin by restarting from step 4.
The gate limits were not set correctly. Restart from step 4.
The gate dynamics could be detected as a collision by the
controller. Set the gate collision sensitivity to be less
sensitive (feature 7 to Status 2 or 3)
The open position of the gate was not confirmed by
pressing the TEST button as in step 21. Restart from step
11.
Mode of operation could be set to condominium, which only
allows the gate to be closed by the auto-close timer.
The safety beams or holiday lockout features could be
activated. Check the IRB and LCK lights, both must be ON
for normal operation.
The link between COMMON and LCK might not be fitted,
when the safety lockout feature id not used.
The link between COMMON and IRB might not be fitted,
when safety beams are not used.
One of the leaf delay modes is selected. The gates can be set to
close simultaneously by setting feature 13 to status 4
Check for, and remove, inputs on the SET terminal.