PROBLEM POSSIBLE CAUSES & SOLUTIONS TO PROBLEM
2
Gate does not move, but the
relays “click” when the unit is
activated:
Page 38
Fault Finding Guide Continued...
3
Gate moves a short distance
and stops:
4
Gate starts closing then stops &
reopens:
Check that you are out of programming mode, SET light
must be OFF.
Check the battery condition with procedure A: Low
battery voltage condition, later in this section.
Check the motor wires.
If STATUS light flashes 4 times then the operator is in
Multiple Collision Mode. Remove & reapply all power, or
wait 60 seconds to reset operation. If required, check with
procedure B: False collision detection, later in this
section.
If the problem persists, the CP75 main controller might
be faulty.
Check the battery condition with procedure A: Low battery
voltage condition, especially if the STATUS light flashes 3
times.
Motor wires use for the SLAVE operator are too thin.
Check for false collisions with procedure B: False collision
detection, later in this section (STATUS light could also
flash 4 times if the number of detected collisions exceeded
the COLLISION COUNTER feature value).
Intermittent IRB trigger. Check that the voltage applied to
the beams are appropriate.
Spurious trigger. Remote with same coding operated in
area, or intermittent short due to possible moisture on the
FRX or TRG inputs.
If the problem is still not solved, the CP75 main controller
might be faulty.
Check collision sensitivity and other causes with procedure
B: False collision detection.