Indoor unit installation
1. Wall Bracket Mounting
A. There are two tabs on the back of the
indoor unit that hold the wall bracket onto
the unit. Press them down with a at head
screwdriver to release the wall bracket from
the back of the unit.
B. Mount the wall bracket ush on structural parts
(studs) of the wall with proper unit clearances
in consideration. (Fig. 1 and Fig. 9)
NOTE: Any space between the unit and the
wall may cause noise or vibration.
C. Screw the wall bracket onto the wall with
type “A” self-tapping screws. If the wall
is made of brick, concrete or the like, drill
1/4” (5mm) diameter pilot holes in the wall.
Use anchors in conjunction with mounting
screws.
NOTE:
• Drill holes in the wall according to the stud
locations and corresponding mounting points
on the actual wall bracket that comes with your
unit. Wall brackets may vary by model and
specications are subject to change.
• It is important to use all screws provided to
secure the wall bracket to the wall.
2. Create Opening for refrigerant and
condensate lines
A. Determine hole position according to the
wall bracket that comes with your unit, the
unit’s required clearances (Fig. 1) and which
direction (left/right) the lines will be routed
from the back of your unit (Fig. 14). Drill
2.5”(65mm) hole angled downward (approx.
45°) toward the outdoors. (Fig. 11).
NOTE: Ensure that neither studs nor plumbing
are located directly behind the proposed hole
location.
B. Always use a conduit to route the piping
through the hole in the wall. Properly seal
the hole after routing the pipes through to
prevent debris, insects, or small animals
from entering.
3. Condensate Drainage
A. Run the drain hose sloping downward. Do not
trap the drain hose. Do not install the drain
hose as illustrated in Fig.12.
B. When extending the drain hose, with locally
purchased hose, insulate the connection
with armaex or similar pipe insulation
material. (Fig. 13)
Fig. 10
Fig. 12
Fig. 11
45°
Fig. 13
Indoor
Outdoor
Wall
Wall Cap
Extension drain-
hose
Wall
Drain hose
Pipe Insulation
Do not block water ow by a rise
Do not put the end of
drain hose into water
Model R L H Hole Diameter
VMH 09 (4.3in) 110mm (7.1in) 180mm
(1.8in)
45mm
02.56 in
(65mm)
VMH 12 (4.3in) 110mm (5.5in) 140mm
VMH 18 (5.3in) 135mm (10.2in) 260mm