Product Brochure

UF-B
600V
9C insulation
Sunlight resistant jacket
Description:
PVC jacketed cable with two or three circuit conductors and an equipment
grounding conductor. Intended for use in accordance with the National
Electrical Code (NEC). Insulated conductors are laid parallel with a bare
grounding conductor.
For use underground as a feeder or branch circuit cable. Direct burial in the
earth is permitted. May be installed in wet, dry, or corrosive locations as
specied by the NEC. May be installed for interior wiring in accordance with
the requirements for nonmetallic-sheathed cable as specied in the NEC.
Materials:
Solid conductors: Soft, uncoated copper per ASTM B3
Stranded conductors: Uncoated copper per ASTM B3 and ASTM B8
Insulation: Color-coded PVC (polyvinyl chloride) rated 90°C dry with nylon
(polyamide) covering.
Jacket: Gray PVC (polyvinyl chloride) jacket applied over and around the
insulated and bare conductors
CerroMax
Underground Feeder Cable
14-2 Solid 14 19 30 190 x 400 63
14-3 Solid 14 19 30 215 x 615 96
12-2 Solid 12 19 30 190 x 450 88
12-3 Solid 12 19 30 220 x 690 137
10-2 Solid 10 24 30 240 x 520 133
10-3 Solid 10 24 30 250 x 750 197
8-2 7 10 35 45 320 x 690 224
8-3 7 10 35 45 350 x 975 325
6-2 7 10 35 45 400 x 720 296
6-3 7 10 35 45 400 x 1,090 433
Conductors
Insulation (+ Nylon)
Thickness (mils)
Jacket
Thickness (mils)
Approx. Cable
Dimension (in)
Approx. Net Wt
Lbs / MFt
AWG # of Conductors
# of Strands
EGC
(AWG)
(Solid)
Data are approximate and subject to normal manufacturing tolerances.
It is the sole responsibility of the end user to determine suitability of this product for its intended use and application.
Features:
Retail Distribution 866.572.3776
Electrical Distribution 800.523.3869
© 2019
Cerrowire Rev 03/2019
A Marmon/Berkshire Hathaway Company
Standards:
UL 493: E26403
UL 83: E15119
ASTM B3
ASTM B8
Surface Print:
Sample: UF-B SUN-RES
12-2 W/G CerroMax (UL)
600V
(Additional information
may be included.)