Specifications

U-ENS00011_99AtypSMSSpec_Rev2.doc
16
Copyright © 2008, Mitsubishi Electric Power Products, Inc.
U-ENS00011 Rev2 12/9/08
2.2.7.2 RS 232 Communication
The UPS shall have, as st andard equipment, an RS 232 smart port allowing the user
to interface the UPS status information to a host computer . Dia mondLink” monitoring
software, or equivalent, shall be available to support the specified operating system.
Field inst alled, and field tested RS 232 additions shall not be accepted.
2.2.7.3 Input Port s
The UPS shall have, as standard equipment, EPO (Emergency Power Of f) and
selectable four (4) input ports. The selectable input ports are the following parameters:
a. Remote Start
b. Remote Stop
c. Power De mand 1
d. Power De mand 2
e. Battery Liquid Low
f. Battery Temperature Abnormal
g. Generator Operation
h. Asynchronous Operation
i. Anther Bus Synch
j. Remote Inverter Supply (MMS)
k. Remote By pass Supply (MMS)
l. Ext Byp dV Str
m. Battery Charger Limit 2
n. Charger Stop
o. External Alarm
p. CB2 Ex
2.2.8 (Option) Remote Status Alarm Panel
The UPS manufacturer shall offer a Remote Status Alarm Panel (RSAP), which shall not
allow any control over the UPS. The RSAP shall have, as st andard equipment, a battery
backup feature allowing it to continue monitoring UPS st atus conditions during power
outage situations. Ride through shall be for a minimum of 8 hours. The RSAP shall act only
as an annunciation panel providing the following alarms/indications as a minimu m:
a. Converter on
b. Load on Inverter
c. Load on Bypass
d. UPS Failure
e. Output Overload
f. UPSinbatteryback-upmode
g. Low battery w hile in back-up mode
2.2.9 (Option) DiamondSync
The UPS manufacture shall offer a Sync circuit which shall allows any two or more
different UPS modules to sync into a master Sync source. The circuit allows both UPS
modules to operate into a common output transfer cabinet and allows the load to continue
to operate without any degradation to the load.