1.7.3 Factory Test
A. The manufacturer shall fully and completely test the system to assure compliance with
the specifications, before shipment.
B. All UPS units shall come equipped with one (1) factory test report included in the UPS
enclosure. The factory test report shall include the following:
1. Series / kVA
2. Serial number
3. Date of test
4. Approved by / Inspected by / Tested by
5. Inspection of construction
6. Checking of wirin g (Black/Red markin g on each connection point)
7. Grounding continuity
8. Insulation strength test
9. Control circuit operation
10. Measurement of steady state characteristics (Voltage/ current/ efficiencies)
11. Transient characteristics (0-100% step load, AC input failure)
12. Overload testing
13. Transfer switch operation
PART 2 PRODUCT
2.1 ELECTRIC CHARACTERISTICS
The UPS shall have the following electrical characteristics:
2.1.1 UPS Output Capacity
The 9900 Series UPS Module is available in the following sizes:
kVA kW
80 72
100 90
150 135
225 202
UPS Module output capacities are in accordance with 0.9 pf lagging.
2.1.2 Battery Capacity
A. Discharge time to end voltage: ___ minutes at full load, 25 degrees C (77 degrees F).
2.1.3 AC Input
A. Nominal input voltage: 480V.
B. Number of phase: 3 phase, 3 wire, plus ground.
C. Voltage range: +15%, -20%.
D. Frequency and range: 60Hz ±10%.
E. Power walk-in time: 20 seconds (0% to 100% load).
F. Power factor:
1. 0.99 typical at 100% load.