-- “----‘I u SYSTEM BOILER Central Heating Faned Flue system Installation and Operating instructions System 40 System 60 “heygFJ& v AA
These instructions are suitable for the following boilers : Britony System 40 Britony System 60
CUSTOMER CARE Chaffoteaux et Maury Ltd , as a leading manufacturer of domestic and commercial water heating appliances, is committed to providing high quality products and a high quality after sales service. If it is necessary to contact an engineer, then telephone your local Chaffoteaux Service Centre. The number can be obtained from the leaflet enclosed in the customer care pack with your boiler or by telephoning the Chaffoteaux Customer Services Department at Telford.
Page CUSTOMER CARE.. ................................................... Guarantee.. .................................................................. Statutory Requirements.. ............................................ Contents ...................................................................... INTRODUCTION.. ....................................................... DESCRIPTION.. .......................................................... Location of components ...........................................
The BRITONY SYSTEM is a fully automatic, wall mounted, low water content boiler. It is a room sealed, fan assisted, balanced flued appliance providing central heating. It has electronic ignition and is suitable for use with all modern electrical control systems. The boiler is designed for sealed systems only and a circulating pump, expansion vessel together with a pressure gauge and safety valve are included within the boiler.
Location of components 1. Air pressure switch 2. Steel chassis complete with expansion vessel 3. Main heat exchanger 4. Combustion chamber 5. Multi- gas burner assembly comprising ignition and ionisation electrodes 6. Automatic air separator and automatic vent 7. Heating circuit flow switch 8. Pump 9. Electrical box 11. Overheat thermostat 12. Gas valve assembly 13. Sealed chamber 14. Flue hood with fan 16, Central heating control thermistor 18. CH Flow isolating valve 19. Two position Selector switch 20.
- 18' 26. 27. 29. 30. 32. 33. 34.
BRITONY SYSTEM type 40 Appliance Cat category . .. . .. . .. .. . . ... . . .. . 60 II 2H 3+ Cat BRITONY SYSTEM type 40 60 Natural gas G20 II 2H 3+ Heat input C/H Maximum in kW . . .. .. ... . . ... . . .. . . Maximum in Btu/h . .. . .. .. . .. .. .. .. 13.41 45764 20.22 69005 Gas rate Maximum in m”/h . . . .. .. .. ...-.. Maximum in ttYh .. . . ... . .. .. . .. .. .. . 1.42 50 2.14 76 Heat output C/H Maximum in kW . . .. .. ... . . ... . . ... . Maximum in Btu/h .. . .. .. . . ... . .. ..
BRITONY SYSTEM type BRITONY SYSTEM type 40 BUTANE L.P.G. G30 Gas rate Maximum in kg/h . .. .. . .. .. . ... . . .. . Maximum in Lbslh .. . .. . .. . .. . . .. . . 1.05 2.32 3.48 Inlet pressure Nominal in mbar . .. . . . ... . . . ... .. .. . Nominal in in wg . .. . . . ... . . ... . .. .. . 28 11.2 28 11.2 1.58 Burner pressure Nominal in mbar . .. . . . ... . . ... . . . .. . Nominal in in wg . .. .. ... . . .. .. . . .. . . Burner injector diameter LPG G30 and G31 in mm . .. . .
Weights With packaging : -BRITONY SYSTEM 40 : -BRITONY SYSTEM 60 : 41.5 kg 41.5 kg Without packaging : -BRITONY SYSTEM 40: -BRITONY SYSTEM 60 : 39.5 kg 39.5 kg Lift weight : -BRITONY SYSTEM 40 : -BRITONY SYSTEM 60 : Outer case dimensions : -Width : 440 (minimum space required 450) - Height : 850 - Depth, 380 / / / / 33.5 kg 33.5 kg / / / :~ , I / , Tails diameter :.
Minimum clearances : - Both sides 5mm - Above casing 170 mm - Below casing 200 - Front ( for servicing) 500 mm - Frdnt (in operation) 5 mm TYPE Cl2 or C42 Fig.
25 Fig. 6 20 Central Heating To be able to supply heating, the selector switch 19 fig. 6 must be turned fully clockwise to ‘ffff position. This will be confirmed by the green indicator light 0 22 fig. 6. When there is a demand for heating (either from the room thermostat or the external programmer) and the boiler temperature control is calling for heat. The pump starts and at a flow rate of 4 Itr/min the central heating flow switch operates allowing the ignition sequence to begin.
After 45 seconds the second stage solenoid 12b fig. 7 opens to allow the full gas rate. If a flame is not detected, after 8 seconds, the security solenoid closes and shuts off the gas. The red lockout indicator bulb 9 24 fig. 6 will light. The central heating flow temperature is controlled by the central heating control thermistor 16 fig. 7.
Location The boiler can be installed on any suitable internal wall. Provision must be made to allow the correct routing of the flue and siting of the terminal to allow the safe and efficient removal of the flue products. The appliance may be installed in any room, although reference must be made to the IEE regulations if it contains a bath or shower. A compartment or cupboard may be used provided that it has been purpose-built or modified for the purpose.
It may be necessary to protect the terminal with a guard if it is accessible and could be damaged. Reference should be made to the Building Regulations for guidance. Suitable guards may be obtained from the following maufacturer: Quinnel Barret & Quinnel Wireworks Old Kent Road London SE15 1NL Tel: 0171 639 1357 Ventilation The room in which the boiler is installed does not require specific ventilation.
Please check that you are familiar with the installation requirements before commencing work.
boiler. Using fig. 15 for reference, connect the gas and water pipes to the valves located at the base of the appliance using the tails provided. There is a 190 mm space between the valves and the wall to make these connections. Provision must be made to fill and recharge the system Fitting the Horizontal Flue The instructions for the elevated horizontal, vertical and biflux (twin pipe) flue options are included with the relevant adapter kits.
Connecting of the boiler to the system - Hinge down the electrical box to gain access to the valves connections. Push in the tabs (P Fig 19) on either side of the boiler and pivot the box forward. - Remove the yellow caps from connecting pipes and connect the boiler to the taps using gaskets provided in the plastic bag. Rubber washer “R” for gas connection.
Making the Electrical Connections Hinge down the electrical box to gain access to the electrical connections. Push in the tabs (P fig. 19) on either side of the boiler and pivot the box forward. Undo the two retaining screws, remove cable clamp. (A fig. 19) remove cover and Connect the live and neutral wires to the multipin plug leaving sufficient earth wire to connect to the earthing point. (B fig. 20).
connector 1 2 Fig. 20 C If using a room thermostat or other external control, they can be connected in place of the link on the multipin plug (fig 21). Connect multipin plug onto into the socket on the power board. Secure the cable using the cable clamp and replace the cover. Earth pillar Fig.
Pre-commissioning Ensure that the system has been adequately flushed. Purge gas supply of air and test for soundness. Carry out final electrical tests to ensure the correct polarity and earthing continuity. Central Heating Open flow and return valves on the boiler.{18 and 29 Fig. 22) Open the automatic air vent (6 Fig. 23) Fill system and vent radiators. Set system pressure and remove filling loop. Check for leaks. Manually check pump is free to turn. Switch on electrical supply.
(see separate servicing leaflet for details) Set the by pass (Refer to system guidance) Re-flush the system to remove any dissolved oils and fluxes. Recharge system pressure and introduce any water treatment as required. Post Commissioning 43 - / /6 Ensure system pressure has been set correctly. Set the by pass. Set boiler thermostat and controls. Set programmer to householder’s requirements. Set external controls. Handing Over to the Householder 19 \ 21 - Fig.
The boiler is suitable for sealed systems only. The maximum working pressure for the appliance is 3 bar. All fittings and pipework connected to the appliance should be of the same standard. Flushing and Water Treatment The performance of the appliance could be impaired by system debris or the effects of corrosion. The system must be flushed thoroughly to remove metal filings, solder, machining oils and other fluxes and greases before connecting the boiler.
By pass and Pump The boiler is fitted with a pre-adjusted by pass. Although adjustment is not normally necessary, the by pass can be reset by turning screw ( D Fig. 9 ) anticlockwise to open the by-pass using the chart below for guidance. If used on a system with thermostatic radiator valves, the flow rate with the thermostatic valves closed should be adjusted to at least 100 l/hr.The chart below indicates the residual head of the pump available for the system. Head and flow rate available m Fig.
Expansion Vessel Filling Point The expansion vessel is pre-charged to 0.7 bar (10 Ib/in2). The vessel is suitable for systems up to 145 litres capacity. For systems of greater capacity an additional expansion vessel will be required. Refer to the chart below and BS 7074 pt 1 or BS 5449. Provision must be made to be able to charge the system on commissioning and to make up any subsequent pressure loss. The method of connection must utilise approved equipment and must comply with the water regulations.
Control panel 19. Two position Selector switch l = Switched OFF ‘Ill1 = Central heating 20. User’s instruction panel. 21. ‘Ill1 Heating flow temperature adjustment 22. 0 Green indicator - Power ON 23. P Orange indicator - Burner ON 24. 9 Red indicator - Lock out /flame failure 25 “RESET” Reset button 26. 0 Pressure gauge Isolating Taps 18. CH Flow isolating valve 27. Gas service tap 29. CH Return isolating valve Fig.
Switching on 1) Check that the gas service tap is opened at the qasmeter and main power is on. 2) Check that pressure in central heating system is above 0.7 bar and below 2.5 bar with the pressure gauge 0 (26). 3) Open the gas tap (27) by turning from right to left. p 4) The boiler is now ready to use. Heating 1) Turn selector switch (19) fully clockwiseto position ‘III1 The green “power on” indicator 0 will light.
Chaffoteaux et Maury are continuously improving their products and therefore reserve the right to change specifications without prior notice and accepts no liability for any errors or omission in the information contained in this document.