Operating instructions

Location - F From an internal or external corner
300 mm
- G Above ground roof or balcony level
300 mm
The boiler can be installed on any suitable internal wall.
_
H From a surface facing the terminal
600 mm
Provision must be made to allow the correct routing of the _ f F
rom another terminal facing the terminal
600 mm
flue and siting of the terminal to allow the safe and efficient
removal of the flue products. The appliance may be
- J From an opening into the dwelling when
under a car port
1200 mm
installed in any room, although reference must be made to
_
K Vertically from a terminal on the same wall
1500 mm
the IEE regulations if it contains a bath or shower. A
_
L Horizontally from a terminal on the same wall
300 mm
compartment or cupboard may be used provided that it has
_
been purpose-built or modified for the purpose. It is not
M fixed by the flat roof ubbink rolux 4GM flue terminal
_
necessary to provide permanent ventilation for cooling
N fixed by a pithed roof ubbink rolux 4GM flue terminal
purposes. Detailed recommendations are given in BS 5440
pt 2. If it is proposed that it is installed in a timber framed
building then reference must be made to British Gas
Document DM2, or advice sought from CORGI.
Flue
The boiler must be installed so that the flue terminal is
exposed to the free passage of external air at all times. It
must not be allowed to discharge into another room or
space such as an outhouse or closed lean-to. The
minimum acceptable clearances are shown below:
- A Directly below an opening, window, etc
- B Below gutters soils pipes or drain pipes
- C Below eaves
- D Below balconies or car port roof
- E From a vertical drain pipe or soil pipe
200mm
200 mm
75 mm
q
1
chaffot-v
--A.A