INSTALLATION
MOUNTING THE CONTROLLER
1. Using appropriate mounting hardware (not supplied), mount
the controller to the wall near the operator at least 5 feet
(1.5m) above floors, landings, steps, or any other adjacent
walking surface. This minimum distance should be measured
from the ground to the bottom of the Stop button.
The installation surface must be smooth and flat.
2. Fasten the entrapment warning placard next to the controller.
To prevent possible SERIOUS INJURY or DEATH from
electrocution:
Be sure power is NOT connected BEFORE installing the door
control station.
To prevent possible SERIOUS INJURY or DEATH from a closing
door:
Install the door control within sight of the door, out of reach of
small children, at a minimum height of 5 feet (1.5 m) above
landings, steps, or any other adjacent walking surface, and
away from ALL moving parts of the door.
Install the control station far enough from the door to prevent
the user from coming in contact with the door while operating
the controls.
Install the entrapment warning placard on the wall next to the
control station in a prominent location visible from the door.
NEVER permit children to operate or play with door control
push buttons or remote controls.
Activate a door ONLY when it can be seen clearly, is properly
adjusted and no obstructions exists in the path the door will
travel.
ALWAYS keep the door in sight until completely closed.
NEVER permit anyone to cross path of a closing door.