OPERATING MODES
This operator is programmed to function in one of six different operating modes.
B2 Mode:
• Works with a 3-Button Control Station wired and 3-Button Radio control, momentary to
open,stop, and close.
• Single Button Control and Single Button Radio momentary to open, stop, close, and stop &
reverse.
• LMEP device required to be learned and connected for downward movement.
• A LMEP obstruction will reverse the door to its Open limit. The safety obstruction can be
overridden with 5 seconds of constant pressure on the Down button.
C2 Mode:
• Works with a 3-Button Control Station wired and 3-Button Radio control, momentary to open,
stop, and constant pressure to close.
• Single Button Control and Single Button Radio momentary to open, stop, and stop & reverse.
• Works without a LMEP device learned, but can operate if a LMEP is learned and connected for
downward movement.
• A LMEP obstruction will reverse the door to its Open limit. The safety obstruction can be
overridden with 5 seconds constant pressure on the Down button.
• Constant Pressure to Close is not an available feature from a remote control device.
T Mode:
• Works with 3-Button Control Station wired and 3-Button Radio control, momentary to open,
stop, close (TTC enabled).
• If the door is at the OLS or at a mid-stop, it will close after the TTC time-out.
• The CLOSE button overrides the TTC for immediate closing of the door. The STOP button
cancels the TTC for that cycle (no automatic motion).
• If the door is obstructed by a safety device, the 3BCS must be used to close the door. TTC will
be disabled if the door reverses from an obstruction.
• Single Button Control and Single Button Radio momentary to open, stop, and stop & reverse.
Constant pressure or momentary input resets the TTC timer.
• A LMEP device is required to be learned and connected for downward movement.
• A LMEP obstruction will reverse the door to its Open limit (no automatic motion). The safety
obstruction can be overridden with 5 seconds of constant pressure on the Down button. The
user can select a desired Timer to Close (TTC) timer under the Timers menu. See page 35 for
Timers setting details.
TS Mode:
• Functions the same as T Mode except it always attempts to close the door from any time the
door is open.
• A LMEP obstruction will reverse the door to its Open limit (TTC will be enabled).
• The controller will make infinite attempts to close the door until the safety obstruction is cleared.
A safety obstruction can be overridden with 5 seconds of constant pressure on the Down button.
D1 Mode:
• Constant contact to open and close with wiring for sensing device to stop
E2 Mode:
• Constant pressure is required on the close button, if a close button is released before the door
is fully closed the door will return to the open position. Use of a safety edge will allow you to
override close button. A single button to open and close cannot be used.
If a user attempts to select an Operating Mode that requires an LMEP, and an LMEP is not
connected, that selection will be unavailable. The following screen will be displayed.
Operating Mode
Requires LMEP