INSTALLATION MANUAL CHAMPION®PLUS SINGLE PACKAGED GAS/ELECTRIC AIR COOLED AIR CONDITIONERS 1-1/2 THROUGH 5 NOMINAL TON CONTENTS GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 DNH: 018 024 030 036 042 048 060 RENEWAL PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 APPROVALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSTALLATION . . . . . . . . . . .
66324-YIM-B-1004 TABLE OF CONTENTS GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 RENEWAL PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 APPROVALS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
66324-YIM-B-1004 GENERAL APPROVALS YORK Model D1NH units are cooling/heating air conditioners designed for outdoor installation. Only gas piping, electric power and duct connections are required at the point of installation. Design certified by CGA and AGA listed as follows: 1. For use as a forced air furnace with cooling unit. 2. For outdoor installation only. The gas-fired heaters have hot surface to pilot ignition. The tubular heat exchangers are aluminized steel. 3.
66324-YIM-B-1004 D 1 N H 0 2 4 N 0 3 6 0 6 V O L T A G E C O D E P R O D U C T C A T E G O R Y 0 6 = 2 5 = 4 5 D = S in g le P a c k a g e A ir C o n d itio n e r P R O D U C T G E N E R A T IO N 2 0 2 0 6 = 8 = 8 /2 8 /2 4 6 0 5 7 5 3 0 3 0 -3 -3 -1 -3 -6 -6 0 -6 0 -6 0 0 1 = 1 s t G e n e r a tio n P R O D U C T ID E N T IF IE R N H = 1 2 S E E R N O M IN A L C O O L IN G C A P A C IT Y (M B H ) G a s H e a t/E le c tr ic 0 1 0 2 0 3 0 3 0 4 0 4 0 6 8 = 4 = 0 = 6 = 2 = 8 = 0 = 1 8
66324-YIM-B-1004 RIGGING OR HANDLING CLEARANCES Care must be exercised when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig unit with slings placed under the unit. Spreader bars of sufficient length should be used across the top of the unit. All units require certain clearances for proper operation and service. Refer to Figure 5 for the clearances required for combustion, construction, servicing and proper unit operation.
6324-YIM-B-1004 ROOF CURB On applications when a roof curb is used, the unit must be positioned on the curb so the front of the unit is tight against the curb. FILTERS Single phase units are shipped without a filter or filter racks and is the responsibility of the installer to secure a filter in the return air ductwork or install a Filter/Frame Kit (1FF0110). A filter rack and a high velocity filters are standard on three phase units. Filters must always be used and must be kept clean.
66324-YIM-B-1004 NOTE: HEAT ANTICIPATOR SHOULD BE SET AT 0.35 AMPS FOR ALL MODELS. THERMOSTAT UNIT TERMINAL STRIP ** = Minimum wire size of 18 AWG wire should be used for all field installed 24 volt wire.
66324-YIM-B-1004 COMPRESSORS Units are shipped with compressor mounting factory-adjusted for shipping. Loosen compressor mounting bolts a half turn before operating unit. TABLE 3: NATURAL GAS APPLICATION DATA AVAILABLE ON MODELS (MBH)1 TEMP. RISE °F AT FULL OUTPUT CAPACITY (MBH) GAS RATE2 FT.3/HR. NUMBER OF BURNERS INPUT3 MIN. MAX.
66324-YIM-B-1004 TABLE 4: PROPANE1 (LP) GAS APPLICATION DATA TEMP. RISE ×F AT FULL AVAILABLE ON MODELS INPUT CAPACITY (MBH)2 GAS RATE3 OUTPUT CAPACITY (MBH) 3 FT. /HR. INPUT4 NUMBER OF BURNERS MIN. MAX. 1-1/2, 2, 2-1/2, 3 TON 45 36 18 2 25 55 2 & 2-1/2 TON 70 56 28 3 30 60 3 TON 70 56 28 3 25 55 3-1/2, 4 & 5 TON 80 64 32 3 25 55 3 TON 90 72 36 4 30 60 3-1/2 TON 108 87 43 4 45 75 4 & 5 TON 108 87 43 4 30 60 4 & 5 TON 135 108 54 5 35 65 1. 2.
66324-YIM-B-1004 .
66324-YIM-B-1004 4. All piping should be cleaned of dirt and scale by hammering on the outside of the pipe and blowing out the loose dirt and scale. Before initial start-up, be sure that all of the gas lines external to the unit have been purged of air. 5. The gas supply should be a separate line and installed in accordance with all safety codes as prescribed under Limitations. After the gas connections have been completed, open the main shut-off valve admitting normal gas pressure to the mains.
66324-YIM-B-1004 TABLE 7: PHYSICAL DATA DNH MODEL EVAPORATOR BLOWER EVAPORATOR COIL CONDENSER FAN CONDENSER COIL CHARGE FILTER CENTRIFUGAL BLOWQER (Dia. x Wd. in.) FAN MOTOR HP (3 Speed) ROWS DEEP FINS PER INCH FACE AREA (Sq. Ft.) PROPELLER DIA. (in.) FAN MOTOR HP NOM. CFM TOTAL ROWS DEEP FINS PER INCH FACE AREA (Sq. Ft.) REFRIGERANT 22 (lbs./oz.) FACE AREA (Sq. Ft.) Size (Nominal) FURNACE SECTION NATURAL GAS BURNER ORIFICE NO. (Drill Size) PROPANE BURNER ORIFICE NO.
66324-YIM-B-1004 VENT AIR OUTLET HOOD BLOWER SERVICE ACCESS COMPARTMENT GAS SUPPLY 1-1/4" DIA. PANEL HOLE (1/2" NPTI CONNECTION) CONDENSER COIL UNIT CONDENSATE CONNECTION 3/4" NPTI (TRAP RECOMMENDED) A 2-3/8 HIGH VOLTAGE CONN. 1-3/8" DIA. KNOCKOUT HIGH VOLTAGE CONN. 7/8" DIA. KNOCKOUT B 3-3/4 REFRIGERANT CONNECTIONS COMBUSTION AIR INLET LOUVERS FRONT 2-1/2 GAS SUPPLY 1-1/4" DIA. KNOCKOUT (1/2" NPTI CONNECTION) LOW VOLTAGE CONN. 1-3/8" DIA.
66324-YIM-B-1004 H IG H V O L T A G E C O N N . 1 -3 /3 2 " D IA . K N O C K O U T 8 -7 /8 1 1 -7 /8 1 9 -1 /4 F R O N T G A S S U P P L Y 1 -5 /8 " D IA . K N O C K O U T (1 /2 " N P T I C O N N E C T IO N ) L O W V O L T A G E C O N N . 1 /8 " D IA .
66324-YIM-B-1004 SEQUENCE OF OPERATION CIRCULATING FAN The unit is controlled by a conventional four wire heating/ cooling thermostat common to this class of equipment. When the thermostat calls for FAN, the thermostat terminal G is energized signaling the circulating fan to run at the heat speed 2 seconds after the G terminal is energized. HEATING When the thermostat calls for HEAT, the thermostat terminal W is energized, energizing the combustion air blower.
66324-YIM-B-1004 3. Remove the control access panel. 4. Turn the gas valve switch to the OFF position. DO NOT FORCE. 5. Replace the control access panel. L IN E P R E S S U R E T A P POST-START CHECK LIST (GAS) After the entire control circuit has been energized and the heating section is operating, make the following checks: 1. Check for gas leaks in the unit piping as well as the supply piping. 2. Check for correct manifold gas pressures. See Checking Gas Input. 3.
66324-YIM-B-1004 HOT SURFACE PILOT INSTRUCTIONS 2. To check, adjust or remove the hot surface pilot assembly, CLOSE THE MAIN MANUAL SHUT-OFF VALVE AND SHUT OFF ALL POWER TO THE UNIT. ADJUSTMENT OF TEMPERATURE RISE The pilot flame should envelope 1/2 inch of the end of the flame sensor and not contain any yellow color, see Figure 7. Lift the pilot and sensor from the assembly. Care must be taken not to damage the pilot or sensor when removing this assembly.
66324-YIM-B-1004 NOTE: To find the BTU input, multiply the number of cubic feet of gas consumed per hour by the BTU content of the gas in your particular locality. (Contact your gas company for this information since it varies widely from city to city.) TABLE 11: GASE RATE - CUBIC FEET PER HOUR1 SECURE OWNER'S APPROVAL When the system is functioning properly, secure the owner's approval. Show him the location of all disconnect switches and the thermostat.
66324-YIM-B-1004 BURNER 6. After brushing is complete, blow all brushed areas with air or nitrogen. Vacuum as needed. At the beginning of each heating season, make a visual check of the main burner flame. If it is not possible to adjust for the proper flame, the burners may need cleaning. 7. Replace parts in the order they were removed in steps 1 through 3. TO CLEAN BURNERS Remove them from the furnace as explained in Burner Instructions. Clean burners with hot water applied along top of the burner.
66324-YIM-B-1004 D1NH Coil Delta P vs Airflow 0.9 D1NH018 D1NH030-36 D1NH042-60 0.8 D1NH024 0.7 D1NH018 ID Coil Delta P 0.6 D1NH024 D1NH030-36 0.5 D1NH042 D1NH048-60 Linear (D1NH018) 0.4 Linear (D1NH024) Linear (D1NH030-36) 0.3 Linear (D1NH048-60) 0.2 0.1 0 400 600 800 1000 1200 1400 1600 1800 2000 2200 Airflow (CFM) FIGURE 14 - D1NH COIL DELTA P VS. AIRFLOW TABLE 12: SUPERHEAT CHARGING TABLE FOR D1NH018 OUTDOOR TEMP.
66324-YIM-B-1004 TABLE 13: SUPERHEAT CHARGING TABLE FOR D1NH024 SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 800 CFM OUTDOOR TEMP. °F INDOOR WB TEMP. (°F) 55 57 59 61 63 65 67 69 71 73 75 65 29.2 29.5 29.7 30.0 30.2 30.5 30.7 31.5 32.2 33.0 33.8 70 25.1 25.8 26.4 27.0 27.7 28.3 29.0 29.8 30.7 31.6 32.5 75 21.0 22.0 23.1 24.1 25.1 26.2 27.2 28.2 29.2 30.2 31.2 80 16.9 18.3 19.7 21.2 22.6 24.0 25.5 26.5 27.6 28.7 29.8 85 12.8 14.6 16.4 18.
66324-YIM-B-1004 TABLE 16: SUPERHEAT CHARGING TABLE FOR D1NH042 OUTDOOR TEMP. °F SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 800 CFM INDOOR WB TEMP. (°F) 55 57 59 61 63 65 67 69 71 73 75 65 25.6 25.8 26.0 26.2 26.5 26.7 26.9 27.4 27.9 28.4 28.9 70 23.3 23.7 24.0 24.4 24.8 25.1 25.5 26.0 26.6 27.1 27.7 75 21.1 21.6 22.1 22.6 23.1 23.6 24.1 24.7 25.3 25.9 26.5 80 18.8 19.4 20.1 20.7 21.3 22.0 22.6 23.3 23.9 24.6 25.2 85 16.5 17.3 18.1 18.
66324-YIM-B-1004 FIGURE 15 - TROUBLESHOOTING TROUBLESHOOTING NOTE: Before troubleshooting, familiarize yourself with the START-UP and CHECKOUT procedures. Troubleshooting of components necessarily requires opening the electrical control box with the power connected to the unit. Use extreme care when working with the live circuits! Check the unit nameplate for the correct line voltage and set the volt meter to the correct range before making any connections with line terminals.
66324-YIM-B-1004 FIGURE 16 - TYPICAL WIRING DIAGRAM D1NH 018, 024, 030, 036, 048 (208/230-1-60 POWER SUPPLY) 24 Unitary Products Group
66324-YIM-B-1004 FIGURE 17 - TYPICAL WIRING DIAGRAM D1NH 030, 036, 042, 048 (208/230-3-60 POWER SUPPLY) Unitary Products Group 25
66324-YIM-B-1004 FIGURE 18 - TYPICAL WIRING DIAGRAM D1NH 030, 036, 042, 048 (460-3-60 POWER SUPPLY) 26 Unitary Products Group
66324-YIM-B-1004 FIGURE 19 - TYPICAL WIRING DIAGRAM D1NH 036, 042, 048, 060 (575-3-60 POWER SUPPLY) Unitary Products Group 27
66324-YIM-B-1004 FIGURE 20 - TYPICAL WIRING DIAGRAM D1NH 060 (208-230-1-60 POWER SUPPLY) 28 Unitary Products Group
66324-YIM-B-1004 FIGURE 21 - TYPICAL WIRING DIAGRAM D1NH 060 (208-230-3-60 POWER SUPPLY) Unitary Products Group 29
66324-YIM-B-1004 FIGURE 22 - TYPICAL WIRING DIAGRAM D1NH 060 (460-3-60 POWER SUPPLY) 30 Unitary Products Group
66324-YIM-B-1004 FIGURE 23 - WIRING DIAGRAM DETAIL B (460 & 575-3-60 POWER SUPPLY)1 1. See Figures 18 and 19. TYPICAL WIRING DIAGRAM NOTES (SEE FIGURES 16, 17, 18 AND 19) 1. All field wiring to be accomplished following city, local and/or national codes in effect at time of installation of this unit. Open all disconnects before servicing this unit. Label all wires prior to disconnection when servicing controls.
Subject to change without notice. Printed in U.S.A. Copyright © 2004 by Unitary Products Group. All rights reserved.