Operating Guide

Model 100199
GENERAL INFORMATION
18
Part No. 101048
HIGH ENGINE TEMP LED
The red LED will be lit if the engine operating temperature
exceeds the factory preset limits. If excessive operating
temperature is detected, the HSB will shut down and re-start
will be disabled. The RED LEDs on the module and enclosure
exterior are lit.
This failure could be the result of an excessive load or high
ambient temperatures. Should this fault occur do the following;
1. Open the enclosure doors to increase air flow throughout
the unit.
2. Check oil level, add oil if required.
3. Inspect the interior and exterior of the enclosure for debris,
leaves, ect., and remove them to increase air flow around
and inside the unit.
4. Once the engine temperature falls into the normal
operating range, generally 30 minutes, follow the reset
procedures in the manuals specific to your model to clear
and correct fault.
5. Close the enclosure doors and the unit is ready to run.
HZ OVER / UNDER SPEED LED
The red LED will be lit if the engine was operating above or
below its preset speed limit. The engine will shut down, and the
LED will remain lit until the generator is repaired and operating
correctly. Appliances connected to the generator circuit could be
damaged from high generator output if the engine is allowed to
operate above its preset limit. If this failure occurs, contact an
authorized Service Dealer or contact Champion Customer Service
at 1-877-338-0999.
LOW OIL LED
The red LED will be lit if the engine oil level has dropped below
the safe operating level. When this happens, the engine will shut
down. Check the engine oil level before attempting to restart the
engine. The engine will not start until the problem is corrected.
OVER CRANK LED
The red LED will be lit if the engine tried to start but was
unable to start in the specied time period. The engine will try
to start five times and if unsuccessful the light will turn on. This
may occur on initial start-up, the fuel system needs to be fully
pressurized to start and operate. Follow reset procedure on page
15.
RUN LED
The green LED will be lit indicating the engine is running.
POWER LED
The green LED will be lit indicating the generator is working
correctly and loads can be connected to it.
ATS CONTROL MODULE
The ATS control module contains the TEST/AUTO/OFF switch and
LEDs that indicate type of power delivery. (Figure 6)
AUTO / AUTO / AUTOMÁTICO
OFF / ARRÊT / APAGADO
TEST / ESSAI / PRUEBA
UTILIDAD
UTILITÉ
UTILITY
CARGA
CHARGER
LOAD
GENSET
GENSET
GENSET
Figure 6
TEST/AUTO/OFF SWITCH
TEST This position allows verication that the generator
power delivery circuit is functional. With the switch in
the TEST position, the engine will start and the ATS will
transfer. The GENSET LED, ATS LED (middle LED) and
LOAD LED should be lit, indicating the generator power
delivery circuit is functional.
AUTO This position allows automatic delivery of power
from the generator if there is a utility outage. With the
switch in the AUTO position and the engine not running,
the UTILITY LED, ATS LED (middle LED) and LOAD LED
should be lit, indicating the household is using utility
provided power.
OFF This position will not allow any power to be
delivered to the ATS when the engine is running.