INSTALLATION MANUAL MODEL #102008 AUTOMATIC TRANSFER SWITCH WITH aXis CONTROLLERTM MODULE REGISTER YOUR PRODUCT ONLINE at championpowerequipment.com or visit championpowerequipment.com READ AND SAVE THIS MANUAL. This manual contains important safety precautions which should be read and understood before operating the product. Failure to do so could result in serious injury. This manual should remain with the product.
102008 - Automatic Transfer Switch with aXis Controller™ Module TABLE OF CONTENTS Table of Contents Installation.......................................... ......... 10 Low Voltage Control Relays............................. ......... 10 Introduction.................................................... 3 Settings on the aXis ControllerTM Module....................... 10 Safety Definitions........................................... 3 WIFI Setup Method................................................
Introduction 102008 - Automatic Transfer Switch with aXis Controller™ Module INTRODUCTION SAFETY DEFINITIONS Congratulations on your purchase of a Champion Power Equipment (CPE) product. CPE designs, builds, and supports all of our products to strict specifications and guidelines. With proper product knowledge, safe use, and regular maintenance, this product should bring years of satisfying service. The purpose of safety symbols is to attract your attention to possible dangers.
Safety Definitions 102008 - Automatic Transfer Switch with aXis Controller™ Module Safety Labels These labels warn you of potential hazards that can cause serious injury. Read them carefully. If a label comes off or becomes hard to read, contact Technical Support Team for possible replacement. HANGTAG/LABEL DESCRIPTION 1681-T-PR BACK 1681-T-PR FRONT ATTENTION ATTENTION ALTERNATE POWER SOURCE AVAILABLE STANDBY GENERATOR ON PREMISES. ALTERNATE POWER SOURCE AVAILABLE STANDBY GENERATOR ON PREMISES.
102008 - Automatic Transfer Switch with aXis Controller™ Module IMPORTANT SAFETY INSTRUCTIONS Important Safety Instructions Before Installation WARNING WARNING Per OSHA 3120 Publication; “lockout/tagout” refers to specific practices and procedures to safeguard individuals from the unexpected energization or startup of machinery and equipment, or the release of hazardous energy during installation, service or maintenance activities. Cancer and Reproductive Harm - www.P65Warnings.ca.
Controls and Features 102008 - Automatic Transfer Switch with aXis Controller™ Module CONTROLS AND FEATURES Read this installation manual before installing your transfer switch. Familiarize yourself with the location and function of the controls and features. Save this manual for future reference. Champion Automatic Transfer Switch with aXis ControllerTM Module 1 2 11 11 3 10 9 12 4 8 11 11 5 6 7 1. aXis Controller 8. Neutral to Ground Bonding Wire 2. Antenna 9. Load L1 and L2 Terminals 3.
102008 - Automatic Transfer Switch with aXis Controller™ Module PANEL BOARD SAFETY INFORMATION Panel Board Safety Information A 120VAC circuit must be installed for battery charging. From ATS fuse block or distribution panel install L1 and N to Wire land # 2 and #3 respectively. As of January 1, 2017, enhanced UL 67 safety requirements took effect, applying to all panel boards and load centers with service equipment applications in accordance with the National Electrical Code, NFPA 70.
Unpacking 102008 - Automatic Transfer Switch with aXis Controller™ Module UNPACKING Location and Mounting Install the ATS as close as possible to utility meter socket. Wires will run between the ATS and main distribution panel, proper installation and conduit are required by code. Mount the ATS vertically to a rigid supporting structure.
Unpacking 102008 - Automatic Transfer Switch with aXis Controller™ Module Wiring the ATS Installation Wiring for ATS Utility Socket NOTICE WARNING The manufacturer recommends that a licensed electrician or an individual with complete knowledge of electricity perform these procedures. US ATS model shown for reference. For Canadian installation, refer to ATS Installation Manual.
Installation 102008 - Automatic Transfer Switch with aXis Controller™ Module INSTALLATION 8. Connect Generator Ground to ground bar. Torque to 35-45 in-lbs. Low Voltage Control Relays The aXis ControllerTM ATS has two low voltage relays that can be used to manage the load of air conditioners or other devices that utilize low voltage controls. The ATS’s two low voltage relays are called AC1 and AC2 and are found on the aXis control board as shown in the picture below.
102008 - Automatic Transfer Switch with aXis Controller™ Module Installation Switch 9. Test HSB with Load NOTICE – On= Test occurs with load. All DIP switches are set to ON by default from the factory. – Off= Test occurs without load. Switch 10. Master/Slave 2. Verify the DIP switches are set for your installation. Adjust as needed. – On= This ATS is the primary or only ATS. <- most common. DIP Switch Settings – Off= This ATS is being controlled by a different aXis ControllerTM ATS.
Installation 102008 - Automatic Transfer Switch with aXis Controller™ Module 7. The time, date, and exercise information have now been setup for the aXis ATS and HSB. You can close your browser and disconnect from the WIFI, or skip to step 2 in the next section “ATS & HSB STATUS USING WIFI”. 4. On the Champion aXis ControllerTM Home Standby Generator Settings Page, set the date and time. Use either the dropdown boxes or the “USE THIS DEVICE’S DATE & TIME” button to set the time and date.
102008 - Automatic Transfer Switch with aXis Controller™ Module Specifications SPECIFICATIONS 6. Return UTILITY circuit breaker to the ON position. ATS will transfer load back to utility and generator will cool down and shut off. aXis ControllerTM Module Automatic Transfer Switch 7. Repeat this process if LMM units are added or removed from the system. Model Number................................................................. 102008 Enclosure Style................................................
WARRANTY* Other Exclusions CHAMPION POWER EQUIPMENT This warranty excludes: 2 YEAR LIMITED WARRANTY – Cosmetic defects such as paint, decals, etc. – Wear items such as filter elements, o-rings, etc. Warranty Qualifications – Accessory parts such as storage covers. To register your product for warranty and FREE lifetime call center technical support please visit: https://www.championpowerequipment.