Wire Land
Points
Function Wire Color
Wire land #1 Ground G (green)
Wire land #2 L1 P (pink)
Wire land #3 N W (white)
Wire land #4 Not Connected- Empty
Wire land #5 B- B (black)
Wire land #6 B+ R (red)
A 120VAC circuit must be installed for battery charging. From ATS
fuse block or distribution panel install L1 and N to Wire land # 1
and #2 respectively.
INPUT 120V - N/L
OUTPUT - CHARGER
Wire Land
Points
Function Wire Color
Wire land #1 N W (white)
Wire land #2 L P (pink)
22-KW (MODEL 100304)
The LEDs on the battery charger indicate whether the charger has
120VAC power, if there is a battery fault and the charger state.
Battery charger rating 24 VDC 7 A.
RECOGNIZED
COMPONENT
XXXXXXX
Certified to CSA Std. C22.2 NO.107.2
Conforms to UL Std.1236
4324-L-PR-A
AUTOMATIC BATTERY CHARGER
CHARGE AUTOMATIQUE DE BATTERIE
CARGADOR DE BATERÍA AUTOMÁTICO
For use with lead acid (LA/SLA), AGM, or Gel batteries.
Not for use with Lithium-ion batteries.
Pour une utilisation avec des batteries au
plomb-acide (LA / SLA), AGM ou gel.
Ne pas utiliser avec des batteries au lithium-ion.
Para uso con baterías de plomo ácido (LA/SLA), AGM o gel.
No para uso con las baterías de iones de litio.
INPUT: 80 - 125 VAC MAX 2.7 A 50/60 Hz
ENTRÉE : 80 - 125 VCA MAX 2,7 A 50 / 60 Hz
ENTRADA: 80 - 125 VCA MAX 2.7 A 50/60 Hz
OUTPUT: 24 VDC 7 A
SORTIE : 24 VCC 7 A
SALIDA: 24 VCC 7 A
SERIAL NO.
NO. DE SERIE
N° DE SÉRIE
MODEL / MODÈLE / MODELO #102652
XXXXXXXXXXXX
K
ColorsAPN 4324-L-PR
Rev A
Size Dieline by CPEC
Artwork Notes
2mm safe margin;
to be printed on
White
substrate.
Revision Changes
---
This artwork belongs to Champion Power Equipment. The contents are confidential and privileged and shall not be disclosed to or used by or for
outside parties without the explicit consent of Champion Power Equipment.
LED SYMBOL DESCRIPTION
DC Voltage Adjustment - Preset
from the factory for proper DC
charger output. No adjustments
necessary.
E. O.
Enforced Output - Press to charge
battery at maximum amperage for
a short period.
Green
Power - Lit to indicate the charger
is receiving 120 VAC and is ready
to charge.
Red
Fault or No Charge - Lit to indicate
a battery charging problem. If this
LED is lit, the LED on the fLex
Controller
®
, “LOW BATTERY” will
also be lit.
Yellow
High Charge - Lit to indicate the
charger is operating above 50%
capacity. Trickle charge and mid
charge LED will also be lit.
Yellow
Mid Charge - Lit to indicate the
charger is near 50% capacity.
Trickle charge LED will also be lit.
Yellow
Trickle Charge - Lit to indicate the
battery is receiving a trickle charge.
No Yellow
Low Trickle Charge - When no
yellow LEDs are lit, the charger is in
low trickle charge state.
A 120 VAC circuit must be installed for battery charging. From ATS
fuse block or distribution panel install 120V circuit to the terminal