Installation Guide
HOME STANDBY GENERATOR- ALL aXis CONTROLLER
®
MODELS
INSTALLATION
36
Wire Land
Points
Function Wire Color
Position #4 Not connected Empty
Position #5 High engine temperature BR (brown)
Position #6 Low oil level/pressure Y (yellow)
Position #7 Not connected Empty
Position #8 Fuel supply valve G/B (green/black)
Position #9 Starter B/W (black/white)
Position #10 Stop L/B (blue/black)
Position #11 B+ W (white)
Position #12 B- G (green)
BOTTOM ROW
There are 12 wire land points in the bottom row, 8 are the same
size, the remaining 4 points are larger, viewed left to right.
100417
FREQ FREQ ATS IN.1 WATR OIL ALT FUEL START STOP B+ B-
FREQ FREQ ATS IN.1 WATR OIL ALT FUEL S
40A FUSE
5A FUSE
The following are the wire land points, function and wire color,
viewed left to right.
Wire Land
Points
Function Wire Color
Position #1 Frequency R (red)
Position #2 Frequency B (black)
Position #3 Not connected Empty
Position #4 Not connected Empty
Position #5 High Engine Temperature BR (brown)
Position #6 Low oil level/pressure Y (yellow)
Position #7 Not connected Empty
Position #8 Fuel supply valve G/B (green/black)
Position #9 Starter B/W (black/white)
Position #10 Stop L/B (blue/black)
Position #11 B+ W (white)
Position #12 B- G (green)
Exterior Warning LED
The exterior of the generator enclosure includes a Warning LED
that illuminates RED when a fault has occurred
The Warning LED provides a visual indicator to homeowners
and service technicians that a fault has occurred, and service is
needed.
The warning LED is located on the back-exterior of the HSB.
14-kW (Model 100515)
22-kW (Model 100304)
Generator ON/OFF Switch
NOTICE
If maintenance or service work is going to be performed on the
generator or the home’s electrical system, accidental startup
is further safeguarded by pulling out the fuse from the aXis
controller panel and disconnecting the batteries.
14-KW (MODEL 100515)
This generator has an ON/OFF switch that when turned off, will
shut down the HSB (if running) and deactivate the aXis controller
preventing future starts. This switch should be used in instances
where the HSB needs to stay off regardless of utility power
presence. When the switch is in the OFF position, the HSB will not
exercise or start for any reason.
When the switch is in the ON position, the aXis controller will be
energized and the HSB will be controlled by the programming of
the aXis controller. The switch needs to be in the ON position in
order for the HSB to be in AUTO mode.