Installation Guide
HOME STANDBY GENERATOR- ALL aXis CONTROLLER
®
MODELS
INSTALLATION
44
Week Day (exercise) - choose week day from 1 to 7.
Set week using
MODE
1= Monday
2= Tuesday
3= Wednesday
4= Thursday
5= Friday
6= Saturday
7= Sunday
for next
Hour (exercise) - choose hours in military time 0 - 23.
Set hour using
MODE
for next
Minute (exercise) - choose the minute from 0-59.
Set minute using
MODE
for next
12. Brownout - allows you to adjust the settings of the aXis
controller
®
to delay start up of the HSB during a brownout or
partial, temporary reduction in system voltage or total system
capacity from your utility. Choose in 30 second increments
(0-300 seconds).
You can cycle through these to select using
MODE
for next
13. When finished, press OFF to save all changes.
PIN LOCATIONS
(On backside of the controller)
CRANK FQ2
I_AUX
I_LOP
I_HWT
FQ1
B-
ALARM
STOP
PREHEAT
FUEL
CHARGER
(D+)
B+
~
Rated Supply:
8~36 VDC (5A Max,)
(Terminal 13 and 15)
MAX WORKING
VOLTAGE
300 VAC
!
DIP1_ENGINE STOP TIME
DIP2_ENGINE STOP TIME
DIP3_SYSTEM FREQUENCY
DIP4_OIL PRESSURE SWITCH TYPE
DIP5_AVR BOOST
DIP6_ENGINE COOLING TIME
vDIP7_ENGINE COOLING TIME
DIP8_IDLE OR PREHEAT
DIP9_PLC ACTIVE
DIP10_STARTER MOTOR STOP RPM
1
915 1011
12
1314
8765432
ON
91 108765432
The pins relate to a function of the aXis Controller. These functions
control the operation of the HSB aXis Controller
®
module. There
are 15 pin locations. Remember the icons on the front side of the
module are only indicators of a run (GREEN) or fault (Red). These
are the designated pin locations, function and wire colors for
reference;
Pin Location Function Wire Color
Pin 1 B+ W(White)
Pin 2
B-
G (Green)
Used for two-wire start
Pin 3 Motor start signal B/W (Black/White)
Pin 4 Fuel valve G/B (Green/Black)
Pin 5 Alarm L/B (Blue/Black)
Pin 6 Stop L (Blue)
Pin 7 Signal to alternator R/B (Red/Black)
Pin 8 Not Connected
Pin 9 Engine High Temp Br (Brown)
Pin 10 Low Oil Pressure Y (Yellow)
Pin 11 Used for two-wire start
Pin 12 Not Connected
Pin 13 Frequency Over/Under R (Red)
Pin 14 Not Connected
Pin 15 Frequency Over/Under B (Black)
DIP Switches (Bottom side of aXis Controller)
The 10 DIP switches relate to a program function of the aXis
Controller. These functions control the operation of the HSB. The
figure below shows the designated factory switch settings for
reference.
CRANK FQ2
I_AUX
I_LOP
I_HWT
FQ1
B-
ALARM
STOP
PREHEAT
FUEL
CHARGER
(D+)
B+
~
Rated Supply:
8~36 VDC (5A Max,)
(Terminal 13 and 15)
MAX WORKING
VOLTAGE
300 VAC
!
DIP1_ENGINE STOP TIME
DIP2_ENGINE STOP TIME
DIP3_SYSTEM FREQUENCY
DIP4_OIL PRESSURE SWITCH TYPE
DIP5_AVR BOOST
DIP6_ENGINE COOLING TIME
vDIP7_ENGINE COOLING TIME
DIP8_IDLE OR PREHEAT
DIP9_PLC ACTIVE
DIP10_STARTER MOTOR STOP RPM
1
915 1011
12
1314
8765432
ON
91 108765432