SPECIFICATIONS
Model 102006 102007 102008 102009 102010
Service Rating Service Entry Rating
Enclosure Style NEMA 3R Outdoor
Maximum Amps 200 150 100
Nominal Volts 120/240
ETL Listed UL STD NO. 1008
CSA STD C22.2 No.
178.1
UL STD NO. 1008
CSA STD C22.2 No.
178.1
Load Management Circuits 4
Weight 43 lbs (19.6 kg)
Height 28 in. (710 mm)
Width 20 in. (507 mm)
Depth 8.3 in. (210 mm)
Technical Specifications
– 22kAIC, no short-time current rating.
– Suitable for use in accordance with the National Electrical Code, NFPA 70.
– Suitable for control of motors, electrical discharge lamps, tungsten filament lamps, and electrical heating equipment, where the sum of
the motor full load ampere ratings and the ampere ratings of the other loads does not exceed the ampere rating of the switch, and the
tungsten load does not exceed 30% of the switch rating.
– Continuous load not to exceed 80% of switch rating.
– Line voltage wiring: Cu or AL, min 60°C, min AWG 1 – max AWG 000, torque to 250 in-lb.
– Signal or Com Wiring: Cu only, min AWG 22 – max AWG 12, torque to 28-32 in-oz.
– All connection lugs are rated AL9CU - 90°C rated
NEMA 3R – This type of enclosed ATS is a weatherproof enclosure and required for exterior installations by code. The enclosure has
knockouts on the bottom and side, and requires water tight connections when installed outside per code. This enclosure can also be used
inside.