Owner`s manual

10
Champion Spas®
OWNER'S MANUAL
110 / 220 VOLT CONVERTIBLE MODELS
• 108*
213* 215* 320*
110 VOLT ELECTRICAL REQUIREME NTS:
*The above models are manufactured with the Champion Spas® 110V/220V convertible spa
pack
.
The unit is factory wired for 220 Volt applications with 4 kW heater operation
.
The model
can be converted for 110 Volt applications and to run with a 1 kW heater operation
.
The 110 Volt model must be connected to a dedicated” 110 Volt 20Amp grounded circuit
.
The term dedicated” means the electrical circuit is not being used for any other electrical items
(lights, appliances, etc.). If the spa is connected to a non-dedicated circuit, overloading will occur
and nuisance tripping of the GFCI breaker switch at the house breaker panel or GFCI cord will
occur
.
Never connect the spa to an extension cord
.
The 110 Volt models may be optionally equipped with a GFCI power cord (approximately 13
feet long). This model must be plugged into a grounding type, 110 Volt 20 Amp receptacle as
shown below
.
shown below.shown below
No other electrical appliances or fixtures should be used on this circuit
.
W
ARNING
WARNINGW
:
The
use
of
any
other
receptacle
or
the
connection
of
the
plug
to
a
220
Volt
service
may
cause
the
spa
pack
to
operate
improperly,
create
the
potential
for
an
electrical
hazard
and
may
void
the
spa
warranty.
Champion Spas® models must be wired in accordance with all local electrical codes. All electrical
work should be done by an experienced, licensed electrician familiar with spa installations
.
N
ote:
As of January 1, 1996 the National Electrical Code (NEC) requires a GFCI (Ground
Fault Circuit Interrupter) on all spa installations.
CORRECT INCORRECT
Data label amperage rating of 16 Amps must use
this type of 20 Amp dedicated receptacle and plug
.
Dedicated
110V,
20A
Receptacle
Dedicated
110V,
15A
Receptacle
Do not use this type
.