Use And Care Manual

Piping System Applications
>> Maximum Working Temperature
180° F (82° C)
>> Maximum Working Pressure
400 PSI at 73° F
100 PSI at 180° F
>> Joining Method
Solvent Weld Joints
Solvent cements must meet ASTM F 493.
Yellow FlowGuard Gold cements may be used
without primer, where approved by code.
Compression fittings with a brass ferrule
may be used.
Threaded Joints
Threading the pipe is NOT recommended
Use CTS CPVC male adapters in cold water
applications only.
Use CTS CPVC x brass threaded transition
fittings for hot water applications.
Do NOT use compression fittings with
brass ferrules to connect to CTS CPVC
pipe or fittings where water temperatures
will exceed 140° F.
CPVC pipe can be used with standard brass
ferrules to make compression connections
where the operating temperature will NOT
exceed 140° F. Apply Teflon (PTFE) tape
over the ferrule to allow for the dissimilar
thermal expansion and contraction
characteristics of the metal ferrule and
the plastic pipe.
FlowGuard Gold
®
Copper Tube Size (CTS) CPVC Pipe and Fittings
For Pressurized Hot & Cold Water Applications
29
FlowGuard Gold CTS CPVC Pipe & Fittings