Use And Care Manual

>> Cure Times
Minimum Cure Time to Test at 100 PSI
Cure times shown are sufficient to complete
a hydrostatic test at 100 PSI with 60%
humidity and cold water. Full cure may take
significantly longer.
Cure times are a function of air temperature,
water temperature, humidity and pipe size.
Increase the cure time for colder temperatures
or higher humidity.
FlowGuard Gold
®
Copper Tube Size (CTS) CPVC Pipe and Fittings
For Pressurized Hot & Cold Water Applications
Size 60˚ F 40˚ F 32˚ F 0 ˚ F
1/2"
3/4"
1"
1-1/4"
1-1/2"
2"
10 min.
10 min.
10 min.
10 min.
15 min.
15 min.
10 min.
15 min.
15 min.
15 min.
15 min.
15 min.
15 min.
15 min.
20 min.
20 min.
30 min.
30 min.
30 min.
30 min.
30 min.
30 min.
45 min.
60 min.
30
FlowGuard Gold CTS CPVC Pipe & Fittings
Piping System Applications